Settings for Grid Support Functions in 208 V Grids


For the grid support functions to work correctly, the following parameters must be set to the specified values on the System Manager user interface.

Parameter

Name

Setting value for SBSE-3.8-US-50

Setting value for SBSE-4.8-US-50

Setting value for SBSE-5.8-US-50

Setting value for SBSE-7.7-US-50

Setting value for SBSE9.6-US-50

Setting value for SBSE11.5-US-50

Inverter.WMax

Set active power limit

3328 W

4160 W

4992 W

6656 W

8320 W

9984 W

Inverter.WMaxIn

Nominal active power WMaxIn

- 3328 W

- 4160 W

- 4992 W

- 6656 W

- 8320 W

- 9984 W

Inverter.VAMaxOut

Nominal apparent power VAMaxOut

3328 VA

4160 VA

4992 VA

6656 VA

8320 VA

9984 VA

Inverter.VAMaxIn

Nominal apparent power VAMaxIn

3328 VA

4160 VA

4992 VA

6656 VA

8320 VA

9984 VA

Inverter.VArMaxQ1

Nominal reactive power VArMaxQ1

1997 var

2496 var

2995 var

3994 var

4992 var

5990 var

Inverter.VArMaxQ2

Nominal reactive power VArMaxQ2

1997 var

2496 var

2995 var

3994 var

4992 var

5990 var

Inverter.VArMaxQ3

Nominal reactive power VArMaxQ3

- 1997 var

- 2496 var

- 2995 var

- 3994 var

-4992 var

-5990 var

Inverter.VArMaxQ4

Nominal reactive power VArMaxQ4

- 1997 var

- 2496 var

- 2995 var

- 3994 var

-4992 var

-5990 var