Requirements for signal cables for backup operation, MFR and rapid shutdown initiator
The cable length and quality affect the quality of the signal. Observe the following cable requirements:
Conductor type: copper wire
Permissible temperature: at least 90°C (194°F)
The conductors must be solid or stranded wire.
Maximum cable length within the inverter: 260 mm (10.3 in)
Conductor cross-section: 0.8 mm² to 1.5 mm² (18 AWG to 16 AWG)
Insulation stripping length: 6 mm (0.24 in)
Nominal voltage: at least 600 V
Maximum length of conductors: 30 m (98 ft)
The cable type and cable-laying method must be appropriate for the application and location.