Requirements for the power cable for secure power supply operation
-
All electrical installations must be carried out in accordance with the applicable electrical standards on site and the National Electrical Code® ANSI/NFPA 70.
Conductor type: copper wire
Permissible temperature: at least 90°C (194°F)
The conductors must be solid or stranded wire.
Maximum cable length within the inverter: 180 mm (7.1 in)
Conductor cross-section when using solid or stranded wire without bootlace ferrules: 1.5 mm² to 6 mm² (6 AWG to 10 AWG)
Conductor cross-section when using bootlace ferrules: 1.5 mm² to 6 mm² (16 AWG to 14 AWG)
Insulation stripping length: 10 mm to 12 mm (0.39 in to 0.47 in)
Maximum length of conductors: 10 m (33 ft)