Requirements for the Battery Power Cables


  • The cables must be made of copper.

  • Maximum cable length within the inverter: 180 mm (7.1 in)

  • Conductor cross-section: 6 mm² to 10 mm² (10 AWG to 8 AWG)

  • Insulation stripping length: 12 mm (0.47 in)

  • Cables can be used with or without bootlace ferrules

  • Maximum permissible cable length between the inverter and the battery: 10 m (33 ft)

  • The cables must be rated for a minimum voltage of 600 V.