Requirements for the Battery Power Cables
The cables must be made of copper.
Maximum cable length within the inverter: 180 mm (7.1 in)
Conductor cross-section: 6 mm² to 10 mm² (10 AWG to 8 AWG)
Insulation stripping length: 12 mm (0.47 in)
Cables can be used with or without bootlace ferrules
Maximum permissible cable length between the inverter and the battery: 10 m (33 ft)
The cables must be rated for a minimum voltage of 600 V.