Connection to the Multifunction Relay
Qualified person
Additionally required material (not included in the scope of delivery):
-
Connection cable
Bootlace ferrules (only for multi-core stranded wire, usable length of the ferrule at least 12 mm)
Requirements for connection cable:
External diameter: 5.3 mm to 7 mm
-
UV-resistant for outdoor use.
Procedure:
- Remove 1 sealing plug from the cable support sleeve.
- Lead the connection cable into the threaded sleeve.
- Dismantle the connection cable 40 mm to 50 mm.
- Strip the insulation on the insulated conductors each by 12 mm.
- When using a multi-core stranded wire, provide the conductors with bootlace ferrules.
- Connect the connection cable to the digital output of the inverter according to the assignment of the terminal block of the COM connector ( > Assignment of Terminal Block of COM Connector).