Connecting the power cable of the battery
Qualified person
NOTICE
Damage to the DC connectors due to the use of contact cleaner of other cleaning agents
Some contact cleaners or other cleaning agents may contain substances that decompose the plastic of the DC connectors.
- Do not use contact cleaners or other cleaning agents for cleaning the DC connectors.
Requirements:
Only use the supplied battery connection cables with DC connectors.
The system must be designed for battery connection cables with a length of 3 m. If this is not possible, the battery connection cable can be extended. Only PV cables with a cross-section of 6 mm² and Sunclix connectors may be used for this purpose.
Procedure:
- Connect the DC connectors to the inverter.
- The DC connectors snap into place.
- Tighten the swivel nuts of the DC connectors to ensure strain relief of the DC cables and compliance with the degree of protection.