Activating the Receipt of Control Signals (Only for Italy)
Qualified person
In order for PV systems in Italy to receive control commands from the grid operator, set the following parameters.
The basic procedure for changing operating parameters is explained in another section ( > Changing Operating Parameters).
Parameter | Value/range | Resolution | Default |
---|---|---|---|
Application ID | 0 to 16384 | 1 | 16384 |
GOOSE-Mac address | 01:0C:CD:01:00:00 to 01:0C:CD:01:02:00 | 1 | 01:0C:CD:01:00:00 |
Procedure:
- Select the parameter group External communication > IEC 61850 configuration.
- In the field Application ID, enter the application ID of the grid operator gateway. You will receive this value from your grid operator. You can enter a value between 0 and 16384. The value 16384 indicates "deactivated".
- In the field GOOSE-Mac address, enter the MAC address of the grid operator gateway from which the inverter is to receive the control commands. You will receive this value from your grid operator.
- The receipt of control signals from the grid operator is activated.