Compatibility with common grid configurations


The following overview shows the compatibility between common grid configurations and the inverters discussed in this document.

Device type

IT

Delta-IT

TN-C

TN-S

TN-C-S

TT

Split phase

Sunny Tripower

STP 12-50

No

No

Yes

Yes

Yes

Yes

No

STP 15-50

No

No

Yes

Yes

Yes

Yes

No

STP 20-50

No

No

Yes

Yes

Yes

Yes

No

STP 25-50

No

No

Yes

Yes

Yes

Yes

No

STP 50-80

No

No

Yes

Yes

Yes

Yes, if UN_PE < 20 V

No

STP 60-80

No

No

Yes

Yes

Yes

Yes, if UN_PE < 20 V

No

STP 125-70

No

No

Yes

Yes

Yes

Yes, if UN_PE < 20 V

No

Sunny Tripower Storage

STPS30-20

No

No

Yes

Yes

Yes

Yes

No

STPS50-20

No

No

Yes

Yes

Yes

Yes

No

Sunny Highpower

SHP 100-21

Yes

Yes

Yes

Yes

Yes

Yes

No

Additional information can be found under the following link: Technical Information "Compatibility between common grid configurations and SMA inverters and SMA charging stations" and at www.SMA-Solar.com.