Allowable Impedance Levels


Allowable Impedance Levels

Impedance (especially resistances of conductors and transformers) between the PV system and the grid cause an increase in voltage measured at the inverter terminals. In order to avoid over-voltage tripping of the inverters and excessive energy losses, AC conductors should be sized to limit the voltage drop between the inverters and the point of common coupling (PCC) to a maximum of 1% of nominal voltage.

In addition, the stability of the inverter control system is affected by the level of impedance (especially inductances of transformers) between the inverters and the point of common coupling (PCC) with the grid.

The maximum allowable impedance level for each inverter model is given in the table below.

Inverter type

Maximum allowable impedance (Zmax)

STP 12-50 / STP 15-50 / STP 20-50 / STP 25-50

33%

STP 125-70

40%

SHP 100-21

50%

13032706188

PV system connected to the grid via multiple transformers

The total system impedance for a given inverter in a PV system can be calculated using the equation below:

13018801292

Legend

Description

ZPCC

ZPCC is the short-circuit impedance based on the short-circuit power available at the PCC

  • Where the total PV system kVA capacity is insignificant relative to the grid capacity at the PCC, grid impedance will be negligibly small and can be excluded from the calculation.

  • When needed, this value is typically provided by the grid operator.

n

n is one of one or more transformers connected in series between the inverter and the PCC.

SPVn

SPVn is the total nominal output power (kVA) of all inverters connected to transformer n.

STRn

STRn is the rated power (kVA) of transformer n.

ZTRn

ZTRn is the short-circuit impedance of transformer n.

Conductor impedance is assumed to be 2% and has been deducted from inverter maximum allowable impedance levels.