Possible protection concepts of the inverters


SMA inverters offer various options to meet the described protection concepts. An overview is provided in the following table.

Implementation of the protection concepts described in the FNN notice is subject to the following restrictions:

  • The Sunny Highpower PEAK3 does not have a unit certificate as per VDE-AR-N 4105, but as per VDE-AR-N 4110, meaning that an external monitoring device is generally required. As the Sunny Highpower PEAK3 has no fast-stop function, an external switch is always required.

Unit certificate in accordance with VDE-AR-N 4105

Unit certificate in accordance with VDE-AR-N 4110

Integrated grid and PV system protection in accordance with VDE-AR-N 41052)

Grid and PV system protection through a monitoring unit 1)

STP 50-80, STP 60-80 (STP X 60)

Yes

Yes

Yes

Yes, with fast stop

STP25-50, STP20-50, STP15-50 and STP12-50 (STP X)

Yes

Yes

Yes

Yes, with fast stop

STP125-70 (STP125)

Yes

Yes

Yes

Yes, with fast stop

STPS30-20, STPS50-20 (STPS X)

Yes

Yes

Yes

Yes, with SMA I/O Module

SHP 100-21 (SHP PEAK3)

No

Yes

No

Yes 3)

1) Recommended at 135 kW to 270 kW, possible up to 500 kW

2) Recommended at 270 kW to 500 kW.

3) No fast stop function available. An external switch must always be used. Parameterize the inverter the same way as the external protective device for setting the protective thresholds.