System Functions of the Data Manager M


If the Data Manager M (EDMM-20) is in the system as a System Manager, the following system functions are available:

  • Control of the active power limitation with SMA inverters

    • An additional energy meter is necessary for this.

    • Via digital signals (e.g. ripple control receiver)

    • Via analog signals

  • PAV,E export limitation

  • Fast stop via digital input

  • Direct selling via Modbus TCP, and in Germany, also via SMA SPOT by coneva

  • Energy management in systems with battery:

    • Increased self-consumption

    • Peak load shaving

    • Multiuse

    • Time of use

  • Load control:

    • Limiting-value based switching of digital outputs

  • Backup/stand-alone grid capability:

    • Battery backup (for this, the Data Manager must be installed behind the active grid disconnection and can then be used for monitoring). In the event of a brief grid failure, the EDMM-20 requires approx. 4 minutes to be operational again after the (stand-alone) grid is restored.

    • Stand-alone grid (for this, the Data Manager must be installed behind the active grid disconnection and can then be used for monitoring). In the event of a brief grid failure, the EDMM-20 requires approx. 4 minutes to be operational again after the (stand-alone) grid is restored.