Configuring the Country Data Set
Qualified person
Set the country data set appropriate for your country or purpose within the first ten feed-in hours via the rotary switches in the inverter. After the first ten feed-in hours, the country data set can only be changed by means of a communication product.
The country data set must be set correctly.
If you select a country data set which is not valid for your country and purpose, it can cause a disturbance in the PV system and lead to problems with the grid operator. When selecting the country data set, you must always observe the locally applicable standards and directives as well as the properties of the PV system (e.g. PV system size, grid-connection point).
- If you are not sure which standards and directives are valid for your country or purpose, contact the grid operator.
Country data set for operation with external decoupling protection
When operating the PV system with an external decoupling protection, the inverter with a firmware version ≤ 2.99.99.R has the country data set Medium-Voltage Directive (Germany) or MVtgDirective and with a firmware version ≥ 3.00.00.R the country data set DE VDE-AR-N4110:2018 generator ext. Decoup. Protection Device or VDEARN4110/18a. These country data sets allow you to extend the operating range of the inverter for voltage and frequency. These country data sets may only be selected if the PV system is disconnected via external decoupling.
- If the country data set for operation is set with external decoupling protection, only operate the inverter with an external three-phase decoupling protection. Without external three‑phase decoupling protection, the inverter will not disconnect from the utility grid when the country-specific standard requirement is exceeded.
Country data sets for all EU countries still not included in the firmware version ≥ 3.00.00.R
Since the new grid connection regulations have not yet been defined for all EU countries, the firmware version ≥ 3.00.00.R does not yet contain country data sets for all EU countries. A generally valid country data set in accordance with EN 50549 is included instead. It can be used in EU countries for which no country data set is available. For individual EU countries, however, it may be temporarily necessary to make adjustments to the locally valid grid connection regulations via parameter settings. This is done on the basis of the country data set previously valid for the country in the firmware version ≤ 2.99.99.R.
- It is decided how to proceed according to the locally valid regulations and the SMA manufacturer's declaration valid for the country of use. Set the generally valid country dataset according to EN 50549 with the firmware version ≥ 3.00.00.R or select the previously valid country dataset with the firmware version ≤ 2.99.99.R. Make the parameter settings according to the manufacturer's declaration.
Change to the names and units of grid parameters to comply with the grid-connection requirements in accordance with Regulation (EU) 2016/631 (valid from April 27, 2019)
To comply with the EU grid-connection requirements (valid from April 27, 2019) the names and units of grid parameters were changed. The change is valid from firmware version ≥ 3.00.00.R. Names and units of grid parameters for inverters with firmware version ≤ 2.99.99.R are not affected by this change and remain valid.
Overview of country data sets and display language for STP xx000TL-30 with a firmware version ≤ 2.99.99.R
A | B | Country data set | Display language | Country |
---|---|---|---|---|
0 | 0 | Default setting | Default setting | Dependent on parameter set |
0 | D | Retained | Polish | Dependent on parameter set |
1 | 0 | VDE0126-1-1 | German | Germany, Switzerland |
1 | 2 | VDE-AR-N4105* | German | Germany |
1 | 6 | VDE-AR-N4105-HP** | German | Germany |
1 | 8 | VDE0126-1-1 | French | Switzerland, France |
1 | B | VFR2014 | French | France |
2 | 0 | VDE0126-1-1 | Italian | Switzerland |
2 | 8 | AS 4777.3 | English | Australia |
2 | A | AS 4777.2 | English | Australia |
3 | 2 | CEI 0-21 external | Italian | Italy |
4 | 0 | RD1699 | Spanish | Spain |
4 | 1 | RD1663-A/661-A | Spanish | Spain |
4 | 4 | Ley2057 | Spanish | Chile |
4 | 8 | PPC | Retained | Greece |
4 | 9 | PPC | English | Greece |
5 | A | G59/3 | English | England |
6 | 0 | EN50438 | German | Various EU countries |
6 | 1 | EN50438 | English | |
6 | 2 | EN50438 | French | |
6 | 3 | EN50438 | Italian | |
6 | 4 | EN50438 | Spanish | |
6 | 5 | EN50438 | Retained | |
6 | 6 | EN50438 | Retained | |
6 | 7 | EN50438 | Retained | |
6 | 8 | EN50438 | Retained | |
6 | 9 | EN50438 | Retained | |
6 | E | NEN-EN50438 | Dutch | Netherlands |
7 | 8 | C10/11/2012 | French | Belgium |
7 | 9 | C10/11/2012 | English | Belgium |
7 | A | C10/11/2012 | German | Belgium |
7 | B | C10/11/2012 | Dutch | Belgium |
A | 0 | Medium-Voltage Directive Germany | German | Germany |
A | 1 | Medium-Voltage Directive Germany | English | Various countries |
A | 2 | Medium-Voltage Directive Germany | French | France |
A | 3 | Medium-Voltage Directive Germany | Spanish | Spain |
A | 4 | Medium-Voltage Directive Germany | Retained | Czech Republic |
A | C | SI4777_HS131_Pf | English | Israel |
B | 0 | MVtgDirective Int. | German | Germany |
B | 1 | MVtgDirective Int. | English | Various countries |
B | 2 | MVtgDirective Int. | French | France |
B | 3 | MVtgDirective Int. | Spanish | Spain |
B | 4 | MVtgDirective Int. | Retained | Czech Republic |
B | 8 | MEA2013 | English | Thailand |
C | 0 | Other standard | English | - |
C | 1 | Other standard | German | |
C | 2 | Other standard | French | |
C | 3 | Other standard | Spanish | |
C | 4 | Other standard | Italian | |
C | 5 | Other standard | Greek | |
C | 6 | Other standard | Czech | |
D | 0 | Island mode 60 Hz | English | - |
D | 1 | Island mode 60 Hz | German | |
D | 2 | Island mode 60 Hz | French | |
D | 3 | Island mode 60 Hz | Spanish | |
D | 4 | Island mode 60 Hz | Italian | |
D | 5 | Island mode 60 Hz | Greek | |
D | 6 | Island mode 60 Hz | Czech | |
E | 0 | Island mode 50 Hz | English | - |
E | 1 | Island mode 50 Hz | German | |
E | 2 | Island mode 50 Hz | French | |
E | 3 | Island mode 50 Hz | Spanish | |
E | 4 | Island mode 50 Hz | Italian | |
E | 5 | Island mode 50 Hz | Greek | |
E | 6 | Island mode 50 Hz | Czech |
* Setting in accordance with VDE-AR-N 4105 for PV systems ≤ 3.68 kVA (Germany)
** Setting in accordance with VDE-AR-N 4105 for PV systems ≤ 13.8 kVA (Germany)
Overview of country data sets and display language for STP xx000TL-30 with a firmware version ≥ 3.00.00.R
A | B | Country data set | Display language | Country |
---|---|---|---|---|
0 | 0 | Default setting | Default setting | Dependent on parameter set |
1 | C | [DE] VDE-AR-N4105:2018 Generators > 4.6 kVA | German | Germany |
1 | D | [DE] VDE-AR-N4110:2018 Generator int. Decoup. Protection Device | German | Germany |
1 | E | [DE] VDE-AR-N4110:2018 Generator ext. Decoup. Protection Device | German | Germany |
2 | 2 | [AT] TOR Generator Typ A V1.0:2019 | German | Austria |
2 | 3 | [AT] TOR Generator Typ B V1.0:2019 System >250 kW | German | Austria |
2 | 4 | [DK] Dansk Energi DK1:2019 LV | English | Denmark |
2 | 5 | [DK] Dansk Energi DK1:2019 LV | German | Denmark |
2 | 6 | [DK] Dansk Energi DK2:2019 LV | English | Denmark |
2 | 7 | [DK] Dansk Energi DK2:2019 LV | German | Denmark |
2 | C | [DE] VDE-AR-N4105:2018 Generators > 4.6 kVA | English | Germany |
2 | D | [DE] VDE-AR-N4110:2018 Generator int. Decoup. Protection Device | English | Germany |
2 | E | [DE] VDE-AR-N4110:2018 Generator ext. Decoup. Protection Device | English | Germany |
3 | 4 | [IT] CEI0-16:2019 System ≤6 MW | Italian | Italy |
3 | 5 | [IT] CEI0-16:2019 System ≤6 MW | German | Italy |
3 | 6 | [IT] CEI0-21:2019 System >11.08 kW ext. Decoup. Protection Device | Italian | Italy |
3 | 7 | [IT] CEI0-21:2019 System >11.08 kW ext. Decoup. Protection Device | German | Italy |
3 | A | [EU] EN50549-1:2018 LV | German | Various EU countries |
3 | B | [EU] EN50549-1:2018 LV | English | Various EU countries |
3 | C | [EU] EN50549-1:2018 LV | French | Various EU countries |
3 | D | [EU] EN50549-1:2018 LV | Italian | Various EU countries |
3 | E | [EU] EN50549-1:2018 LV | Spanish | Various EU countries |
3 | F | [EU] EN50549-1:2018 LV | Dutch | Various EU countries |
4 | A | [EU] EN50549-2:2018 MV | German | Various EU countries |
4 | B | [EU] EN50549-2:2018 MV | English | Various EU countries |
4 | C | EU EN50549-2-18 | French | Various EU countries |
4 | D | [EU] EN50549-2:2018 MV | Italian | Various EU countries |
4 | E | [EU] EN50549-2:2018 MV | Spanish | Various EU countries |
4 | F | [EU] EN50549-2:2018 MV | Dutch | Various EU countries |
5 | C | [UK] ENA-EREC-G99/1:2018 | English | Great Britain |
7 | C | [BE] C10/11-LV2:2018 LV >10kVA | French | Belgium |
7 | D | [BE] C10/11-LV2:2018 LV >10kVA | English | Belgium |
7 | E | [BE] C10/11-LV2:2018 LV >10kVA | German | Belgium |
7 | F | [BE] C10/11-LV2:2018 LV >10kVA | Dutch | Belgium |
8 | 0 | [BE] Synergrid C10/11:2019 LV Generators int. Decoup. Protection Device | French | Belgium |
8 | 1 | [BE] Synergrid C10/11:2019 LV Generators int. Decoup. Protection Device | English | Belgium |
8 | 2 | [BE] Synergrid C10/11:2019 LV Generators int. Decoup. Protection Device | German | Belgium |
8 | 3 | [BE] Synergrid C10/11:2019 LV Generators int. Decoup. Protection Device | Dutch | Belgium |
8 | 4 | [BE] Synergrid C10/11:2019 LV Generators ext. Decoup. Protection Device | French | Belgium |
8 | 5 | [BE] Synergrid C10/11:2019 LV Generators ext. Decoup. Protection Device | English | Belgium |
8 | 6 | [BE] Synergrid C10/11:2019 LV Generators ext. Decoup. Protection Device | German | Belgium |
8 | 7 | [BE] Synergrid C10/11:2019 LV Generators ext. Decoup. Protection Device | Dutch | Belgium |
8 | 8 | [BE] Synergrid C10/11:2019 MV Generators int. Decoup. Protection Device | French | Belgium |
8 | 9 | [BE] Synergrid C10/11:2019 MV Generators int. Decoup. Protection Device | English | Belgium |
8 | A | [BE] Synergrid C10/11:2019 MV Generators int. Decoup. Protection Device | German | Belgium |
8 | B | [BE] Synergrid C10/11:2019 MV Generators int. Decoup. Protection Device | Dutch | Belgium |
8 | C | [BE] C10/11-MV1:2018 MV | French | Belgium |
8 | D | [BE] C10/11-MV1:2018 MV | English | Belgium |
8 | E | [BE] C10/11-MV1:2018 MV | German | Belgium |
8 | F | [BE] C10/11-MV1:2018 MV | Dutch | Belgium |
9 | 0 | [BE] Synergrid C10/11:2019 MV Generators ext. Decoup. Protection Device | French | Belgium |
9 | 1 | [BE] Synergrid C10/11:2019 MV Generators ext. Decoup. Protection Device | English | Belgium |
9 | 2 | [BE] Synergrid C10/11:2019 MV Generators ext. Decoup. Protection Device | German | Belgium |
9 | 3 | [BE] Synergrid C10/11:2019 MV Generators ext. Decoup. Protection Device | Dutch | Belgium |
Procedure:
- Determine the rotary switch position for your country and purpose. Call up the Technical Information "Overview of the Rotary Switch Settings" at www.SMA-Solar.com.
- Ensure that the inverter is disconnected from all voltage sources and that the enclosure lid is removed ( > Disconnecting the Inverter from Voltage Sources).
- Set the rotary switches A and B to the required position using a flat-blade screwdriver (blade width: 2.5 mm).
DANGER
Danger to life due to high voltages
- The inverter will adopt the setting after commissioning. This can take up to 5 minutes.