Reducing the Attenuation of Ripple Control Signals


Qualified person

By setting certain parameters, the attenuation of three-phase parallel ripple control frequencies ranging from 1000 Hz to 1100 Hz can be avoided. The parameters must only be set in consultation with the responsible grid operator.

The basic procedure for changing operating parameters is explained in another section Changing Operating Parameters).

Requirements:

  • The firmware version of the inverter must be at least 2.81.07.R.

Procedure:

  1. Set the following parameters:
  2. SMA Data/RS485

    Definition

    Unit

    Range

    Value to be set

    RplDet-NBS-Gain

    Ripple control signal detection, amplification of narrow-band backup

    V/A

    0 to -10

    -9

    RplDet-NBS-Damp

    Ripple control signal detection, attenuation of narrow-band backup

    p.u.

    -

    0.1

    RplDet-NBS-Hz

    Ripple control signal detection, frequency of the narrow-band backup

    Hz

    1000 to 1100

    Must be specified by the grid operator