Mounting the Inverter


Qualified person

Additionally required mounting material (not included in the scope of delivery):

  • At least two screws suitable for the support surface (diameter: 10 mm at maximum)
  • At least two washers that are suitable for the screws (diameter: 30 mm at maximum)
  • If necessary, two screw anchors suitable for the support surface and the screws
  • For transporting the inverter with a crane: two eye bolts suitable for the weight of the inverter (size: M10)
  • To secure the inverter from being lifted off: two screws suitable for the support surface, two washers suitable for the screws and - depending on the support surface - two screw anchors suitable for the support surface and the screws

CAUTION

Risk of injury when lifting the inverter, or if it is dropped

The inverter weighs 61 kg. There is risk of injury if the inverter is lifted incorrectly or dropped while being transported or when attaching it to or removing it from the wall mounting bracket.

  1. Transport the inverter always as described below.

CAUTION

Risk of burns due to hot enclosure parts

Some parts of the enclosure can get hot during operation.

  1. Mount the inverter in such a way that it cannot be touched inadvertently during operation.

Procedure:

  1. CAUTION

    Risk of injury due to damaged cables

    There may be power cables or other supply lines (e.g. gas or water) routed in the wall.

    1. Ensure that no lines are laid in the wall which could be damaged when drilling holes.
  2. Align the wall mounting bracket horizontally on the wall and use it to mark the position of the drill holes. Use at least one hole on the right-hand and left-hand side in the wall mounting bracket.
  3. If the inverter is to be secured from being lifted off of the wall mounting bracket, mark the position of the drill holes for the screw that attaches the inverter to the wall mounting bracket. Observe the dimensions of the two anchoring points at the bottom of the inverter rear panel.
  4. Set the wall mounting bracket aside and drill the marked holes.
  5. Insert screw anchors into the drill holes if the support surface requires them.
  6. Secure the wall mounting bracket horizontally using screws and washers.
  7. 851014028
  8. Hook the inverter into the wall mounting bracket.
  9. If the inverter has been transported with a crane, remove the eye bolts from the threads on the top of the inverter and reinsert the filler plugs.
  10. 853288204
  11. Remove all six screws from the lower enclosure lid using an Allen key (AF 3).
  12. 853288588
  13. Flip the lower enclosure lid up and remove it.
  14. 853288972
  15. In order to secure the inverter from being lifted off the wall accidentally, attach it to the wall with suitable mounting material. Use both of the lower drill holes on the rear panel of the inverter.
  16. Ensure that the inverter is securely in place.