Event 168
Event message:
Battery issuing pre-charge error
Explanation:
The battery voltage is too low during the precharge phase.
LED signal on battery module:
The 6th LED is glowing red
Corrective measures:
Switch off the DC circuit-breaker on the BMS unit.
Stop and then restart the inverter.
Wait a few seconds.
Switch the DC circuit-breaker on the BMS unit back on.
Check the DC cables and ensure that there is not a reverse polarity error
If the error persists, contact Service.