Sunny Island Inverter Selection


Power-temperature curve

The active power specified for the Sunny Island is dependent on the ambient temperature (see the Sunny Island inverter datasheet for the power to temperature ratio). If constantly high ambient temperatures are to be expected at the planned installation site, a Sunny Island with a higher rated power than is necessary for the load requirements should be selected.

Device type

Rated power

Power for 30 minutes at 25°C

Application

Single System

Single-phase single-cluster system

Three-phase single-cluster system

Multicluster system

SI4.4M-12 / SI4.4M-13
(Sunny Island 4.4M)

3300 W

4400 W

yes

no

yes

no

SI6.0H-12 / SI6.0H-13
(Sunny Island 6.0H)

4600 W

6000 W

yes

yes

yes

yes

SI8.0H-12 / SI8.0H-13
(Sunny Island 8.0H)

6000 W

8000 W

yes

yes

yes

yes