Operating Procedure with Generators with External Generator Control


Event or state

Result

Internal transfer relay

The generator management system requests the generator.

The Sunny Island signalizes to the external generator control that the generator has been requested.

Open, the stand-alone grid is not connected to the generator.

The external generator control starts the generator.

The generator voltage builds up.

The warm-up time set at the external generator control begins.

The generator management system measures the time until the external generator control signals to the Sunny Island that the warm-up time has expired. If a maximum time is exceeded, the generator management system terminates the generator start.

The external generator control signalizes to the Sunny Island that its warm-up time has successfully expired.

The Sunny Island synchronizes the stand-alone grid with the generator voltage.

The stand-alone grid is synchronized.

The Sunny Island connects the stand-alone grid to the generator.

Closed, the stand-alone grid is connected to the generator.

The stand-alone grid is connected to the generator.

The generator feeds current into the stand-alone grid.

The generator management system starts the minimum run time.

The minimum run time is running.

Even if the generator management system no longer requests the generator, the stand-alone grid remains connected to the generator.

The minimum run time ends.

If the generator management system continues to request the generator, the stand-alone grid remains connected to the generator.

The generator management system no longer requests the generator.

The Sunny Island supplies the stand-alone grid and carries out load-free disconnection of the generator from the stand-alone grid.

Open, the stand-alone grid is not connected to the generator.

The generator management system signalizes to the external generator control that the generator is no longer being requested.

The power-down time set at the generator management system begins.

The power-down time is running.

During the power-down time, the generator management system cannot request the generator again and the Sunny Island cannot reconnect the stand-alone grid to the generator.

The power-down time ends.

The external generator control stops the generator.

The external generator control signalizes to the Sunny Island that its power-down time has expired.

The generator management system starts the minimum stop time.

The minimum stop time is running.

The Sunny Island suppresses every generator request. It is also not possible to perform a manual start at the Sunny Island.

The minimum stop time ends.

The generator management system can request the generator.

The generator can be started at the Sunny Island.