Requirements on the SPS OUT AC cable for connection to the inverter
- Conductor type: copper wire
- The conductors must be solid or stranded wire.
- Conductor cross-section when using solid or stranded wire without bootlace ferrules: 1.5 mm² to 2.5 mm²
- Conductor cross-section when using bootlace ferrules: 1.5 mm² to 2.5 mm²
- External diameter: 8 mm to 9.5 mm
- Insulation stripping length: 8 mm to 10 mm
- Maximum length of conductors: 30 m