Requirements on the SPS OUT AC cable for connection to the inverter


  • Conductor type: copper wire
  • The conductors must be solid or stranded wire.
  • Conductor cross-section when using solid or stranded wire without bootlace ferrules: 1.5 mm² to 2.5 mm²
  • Conductor cross-section when using bootlace ferrules: 1.5 mm² to 2.5 mm²
  • External diameter: 8 mm to 9.5 mm
  • Insulation stripping length: 8 mm to 10 mm
  • Maximum length of conductors: 30 m