Backup output (battery-backup operation) during off-grid mode (only applies to System Manager)
STPH5-60 / STPH6-60 / STPH8-60 / STPH10-60 | STPH12-60 / STPH15-60 | |
|---|---|---|
Rated power 1~ (at 230 V, 50 Hz) | 3680 W | 5000 W |
Rated power 3~ (at 230 V, 50 Hz) | 10000 W | 15000 W |
Maximum apparent AC power (at 230 V, 50 Hz) | 10000 VA | 15000 VA |
Maximum output current | 16 A | 22.7 A |
Maximum output current < 2s | 32 A | 43.5 A |
Maximum output current < 5s | 24 A | 32.6 A |
Nominal grid voltage AC | 230 V / 400 V | |
AC grid frequency | 50 Hz | |
Switching mode | Automatic | |
Switching time to backup operation | approx. 1 s | |