Mounting the Sunny Multigate on the Wall
Additionally required mounting material (not included in the scope of delivery):
- Distribution box complying with the installation site requirements according to degree of protection IP20
- Four screws suitable for the size of the press-out brackets of the Sunny Multigate and for the material of the distribution box. The maximum permissible height of the screw head of 6 mm must not be exceeded.
Procedure:
- To avoid contact between screw and conductor, only use screws with a maximum head height of 6 mm for mounting on the brackets.
- Press the four brackets on the back side of the Sunny Multigate out from the inside.
- The brackets snap audibly into place.
- Mark the drill holes using the brackets as a template.
- Drill the holes.
- Insert screws with a maximum head height of 6 mm through the brackets and tighten. Make sure not to damage the brackets.
- Make sure that the Sunny Multigate is securely in place.
WARNING
Danger to life due to electric shock
If screws or conductors on the connecting terminal plate are touched, there is a risk of electric shock.