Disconnecting the AC Field Plug

Removing and reassembling the AC field plug is only possible within 72 hours
- In total, the AC field plug may at maximum be removed three times and only within the first 72 hours after the first assembly.
- After the period of 72 hours has expired, the AC field plug must not be removed.
- The cable must be shortened again before the assembling.
Procedure:
- Ensure that the circuit breaker is switched off and that it cannot be reconnected.
- Make sure that the PV modules are covered.
- Unlock and remove the AC field plug from the connector of the inverter AC cable. Hook a flat-blade screwdriver (blade width: 4 mm) into the wide slot at the AC field plug and lever it open. At the same time, pull out the AC connector.
- If necessary, disassemble the AC field plug:
-
Loosen the screw connection of the plug enclosure.
-
Remove the seal from the opening of the thread. Make sure not to damage the fins of the plug enclosure.
-
Detach the plug enclosure from the insulator. Insert a flat-blade screwdriver (blade width: 4 mm) into the small slot of the plug enclosure and unlock the fastening clamps until the insulator is detached from the plug enclosure.
-
Loosen all three screws using a screwdriver and remove the conductors.
-
Prior to reassembling the AC field plug, shorten the cable.
-
If necessary, reassemble the AC field plug ( > Assembling the AC Field Plug).
DANGER
Danger to life due to electric shock
Do not disconnect the AC field plug under load.