Configuring the Country Data Set
By default, the Sunny Multigate is set to a specific country data set. You can find the country data set to which the Sunny Multigate has been set on the enclosed supplementary sheet with the default settings or on the type label. Each country data set contains various operating parameters, which can be individually set according to the respective country. You can change the parameters by means of a communication product.

The country data set must be set correctly.
If you select a country data set which is not valid for your country and purpose, it can cause a disturbance in the PV system and lead to problems with the grid operator. When selecting the country data set, you must always observe the locally applicable standards and directives as well as the properties of the PV system (e.g. PV system size, grid-connection point).
- If you are not sure which country data set is valid for your country or purpose, contact your grid operator for information on which country data set is to be configured.
The basic procedure for changing operating parameters is explained in another section ( > Changing Operating Parameters).
Procedure:
-
Select the parameter Default or Set country standard and adjust the required country data set.