Preparing inverter without roof for installation of the sound absorber
NOTICE
Risk of corrosion on the inverter enclosure due to moisture during installation
Moisture on the inverter prior to installation of the sound absorber can penetrate inside the inverter. This can result in corrosion.
- Protect the inverter without roof from ambient influences such as direct rain or snow. Use a tarpaulin or store the inverter in a sheltered place.
- Ensure that the inverter is dry before the sound absorber is installed.
- Ensure that no moisture has penetrated the openings in the roof.
Procedure:
- Ensure that the top of the inverter is dry.
- On the AC side remove the 5 screws, 10 silicone washers and 10 washers on the top of the inverter, and dispose of them. When doing this, ensure that all mounting material has been removed from the inverter.
- On the DC side remove the 5 screws, 10 silicone washers and 10 washers on the top of the inverter, and dispose of them. When doing this, ensure that all mounting material has been removed from the inverter.