Connecting the AC Cable


Qualified person

Requirements:

  • The grid voltage must be within the permissible range. The exact operating range of the inverter is specified in the operating parameters .

Procedure:

  1. Disconnect the miniature circuit breaker from all 3 line conductors and secure against reconnection.
  2. 11629942156
  3. Ensure that the DC load-break switch is in the O position.
  4. 11629942540
  5. If your country requires the DC load-break switch to be protected against reconnection, secure the DC load-break switch against reconnection with a padlock.
  6. 11629942924
  7. Unscrew the screws of the enclosure lid with a Torx screwdriver (TX 25) and remove the enclosure lid carefully forward.
  8. Remove the adhesive tape from the enclosure opening for the AC connection.
  9. 11629943308
  10. Insert the cable gland M32x1.5 into the opening and tighten it with the counter nut from the inside.
  11. Route the AC cable into the inverter through the cable gland. If necessary, slightly loosen the swivel nut of the cable gland.
  12. Dismantle the AC cable.
  13. Strip off the conductor insulation by 18 mm to 20 mm each.
  14. If necessary, provide each conductor with a bootlace ferrule.
  15. 11629943692
  16. Press the locking lever of terminal PE upward, guide conductor PE into the terminal, and press locking lever downward again.
  17. 11629944076
  18. For connection without a neutral conductor, use the jumper provided to bridge terminal blocks PE and N. For this, press the locking levers of terminals PE and N upward, guide the jumper into the terminals, and press the locking levers downward again.
  19. 11629944460
  20. Press the locking levers of terminals L1, L2, L3, and if applicable N upward, guide conductors L1, L2, L3, and if applicable N into the terminals according to the labeling, and press the locking levers downward again.
  21. Ensure that the correct conductors are assigned to all the terminals.
  22. Ensure that all conductors are securely in place.