Decommissioning the Product
Qualified person
To decommission the inverter completely upon completion of its service life, proceed as described in this Section.
CAUTION
Risk of injury due to weight of product
Injuries may result if the product is lifted incorrectly or dropped while being transported or mounted.
- Transport and lift the product carefully. Take the weight of the product into account.
- Use the carrying handles or hoist when transporting the product. To attach the hoist system, eye bolts must be screwed into the threads provided, which are located on the right and left of the product's mounting lugs.
- Wear suitable personal protective equipment for all work on the product.
Procedure:
- Disconnect the inverter from all voltage sources ( > Disconnecting the Inverter from Voltage Sources).
- Wait 30 minutes for the enclosure to cool down.
- If the DC terminal cover is present, disassemble the DC terminal cover. To do so, unscrew the M5x14 screws (TX25).
- Remove the AC cable from the inverter. Press the locking levers all the way upward and pull the conductors out of the terminal blocks for the AC connection.
- Press down the locking levers of the terminal blocks for the AC connection.
- If additional grounding is connected, remove it.
- If the multifunction relay is used, remove the connection cable from the inverter.
- If other cables (e.g. network cables or signal cables) are connected, remove them from the inverter.
- If a module is plugged in, remove it from the inverter.
- Close the enclosure lid of the inverter.
- If the inverter is protected against theft, open the padlock and remove it.
- Unscrew the two M5x14 screws protecting the inverter from being lifted off with a screwdriver (TX25).
- Remove the inverter by lifting it up and off the wall mounting bracket.
- If the inverter is to be stored or shipped in packaging, pack the inverter. Use the original packaging or packaging that is suitable for the weight and dimensions of the inverter.
CAUTION
Risk of burns due to hot enclosure parts