AC cable requirements
Conductor type: copper wire
The conductors must be solid or fine-stranded. When using fine-stranded wire, bootlace ferrules can be used.
Outer diameter: 14 mm to 25 mm
Conductor cross-section grounding conductor: 6 mm² to 16 mm² (The minimum conductor cross-section of 6 mm² is only permitted if additional grounding is connected. If no additional grounding is connected, the minimum conductor cross-section is 10 mm².)
Conductor cross-section of line conductor and neutral conductor: 6 mm² to 16 mm²
Insulation stripping length: 18 mm to 20 mm
Sheath stripping length: 120 mm to 150 mm
The cable and conductor cross-sections must always be dimensioned according to the local and national directives and within the range specified by the manufacturer (SMA Solar Technology AG)." If the manufacturer (SMA Solar Technology AG) requires a higher conductor cross-section than the standard, the range of the manufacturer must be observed. Examples of factors influencing cable dimensioning are: nominal AC current, type of cable, routing method, cable bundling, ambient temperature and maximum desired line losses (for calculation of line losses, see the design software "Sunny Design" from software version 2.0 at www.SMA-Solar.com).