Connect signal source to MFR
Qualified person
Requirements:
The technical requirements of the multifunction relay must be met ( > Technical Data).
Procedure:
- Disconnect the inverter from all voltage sources ( > Disconnecting the Inverter from Voltage Sources).
- Unscrew the swivel nut from the cable gland.
- Remove the four-hole cable support sleeve from the cable gland.
- Remove the plug from one of the enclosure openings and cut into the enclosure opening with a utility knife.
- Insert the cable into the enclosure opening.
- Press the four-hole cable support sleeve with the cable into the cable gland and guide the cable to slot MFR. Ensure that the unused enclosure openings of the four-hole cable support sleeve are sealed with sealing plugs.
- Strip 6 mm of the cable insulation at maximum.
- Connect the cable to the 3-pole terminal block according to the operating mode. Ensure that the conductors are plugged completely into the terminal points up to their insulation.
- Insert the 3-pole terminal block with the connected conductors into slot MFR.
- Ensure that the terminal block is securely in place.
- Ensure that all conductors are correctly connected.
- Ensure that the conductors sit securely in the terminal points. Tip: To release the conductors, open the terminal points using a suitable tool.
- Tighten the swivel nut on the cable gland hand-tight.