Adjustable Parameters


You can change the following parameters for voltage and frequency monitoring with a communication product (e.g. Sunny Explorer) Changing Operating Parameters).

The voltage specifications are based on the line-to-neutral voltages. If the set values are present as line-to-line voltages, these have to be converted to line-to-neutral voltages.

Name

Value/range

Default value

Voltage monitoring of upper maximum threshold as RMS value

277 V to 332.4 V

332.4 V

Voltage monitoring median maximum threshold (Overvoltage/Fast)

277.0 V to 332.4 V

332.4 V

Voltage monitoring lower maximum threshold (Overvoltage/Slow)

277.0 V to 304.7 V

304.7 V

Voltage monitoring upper minimum threshold (Undervoltage/Slow)

138.5 V to 277.0 V

243.8 V

Voltage monitoring of median minimum threshold (Undervoltage/Fast)

138.5 V to 277.0 V

138.5 V

Voltage monitoring of lower minimum threshold as RMS value

138.5 V to 277 V

138.5 V

Voltage monitoring of upper max. thresh. as RMS value for tripping time

0.1 s to 59 s

0.2 s

Voltage monitoring median max. threshold trip.time (Overvoltage/Fast, maximum time)

0.1 s to 59 s

0.16 s

Voltage monitoring lower max. threshold trip. time (Overvoltage/Slow, maximum time)

0.1 s to 60 s

1.0 s

Voltage monitoring upper min. threshold trip. time (Undervoltage/Slow, maximum time)

0.1 s to 60 s

2.0 s

Voltage monitoring median min. threshold trip.time (Undervoltage/Fast, maximum time)

0.1 s to 60 s

0.16 s

Voltage monitoring of lower min.threshold as RMS value for tripping time

0.1 s to 60 s

0.2 s

Frequency monitoring upper minimum threshold (Underfrequency)

44 Hz to 60 Hz

59.3 Hz

Frequency monitoring lower maximum threshold (Overfrequency)

50 Hz to 66 Hz

60.5 Hz

Frq. monitoring upper min. threshold trip. time (Underfrequency, maximum time)

0.1 s to 1000 s

0.16 s

Frq. monitoring lower max. threshold trip. time (Overfrequency, maximum time)

0.1 s to 1000 s

0.16 s