Event Messages
Event number | Message, cause and corrective measures |
|---|---|
101 to 103 | Grid incident The grid voltage or grid impedance at the connection point of the inverter is too high. The inverter has disconnected from the utility grid. Corrective measures:
|
202 to 203 | Grid incident The utility grid has been disconnected, the AC cable is damaged or the grid voltage at the connection point of the inverter is too low. The inverter has disconnected from the utility grid. Corrective measures:
If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must agree with an adjustment of the voltage at the feed-in point or with a change of the monitored operating limits. If the grid voltage is permanently within the permissible range and this message is still displayed, contact the Service. |
301 | Grid incident The ten-minute average value of the grid voltage is no longer within the permissible range. The grid voltage or grid impedance at the connection point is too high. The inverter disconnects from the utility grid to maintain power quality. Corrective measures:
|
401 | Grid incident The inverter is no longer in grid-parallel operation. The inverter has stopped feeding into the utility grid. Corrective measures:
|
404 | Grid incident The inverter is no longer in grid-parallel operation. The inverter has stopped feeding into the utility grid. Corrective measures:
|
501 | Grid incident The power frequency is not within the permissible range. The inverter has disconnected from the utility grid. Corrective measures:
|
601 | Grid incident The inverter has detected an excessively high proportion of direct current in the grid current. Corrective measures:
|
701 | Frequency not permitted > Check parameter The power frequency is not within the permissible range. The inverter has disconnected from the utility grid. Corrective measures:
|
901 | Grounding connection missing > Check connection The grounding conductor is not correctly connected. Corrective measures:
|
1302 | Waiting for grid voltage > Installation failure grid connection > Check grid and fuses The inverter has detected an error in the AC cabling. The inverter cannot connect to the utility grid. Corrective measures:
|
1501 | Reconnection fault grid The changed country data set or the value of a parameter you have set does not correspond to the local requirements. The inverter cannot connect to the utility grid. Corrective measures:
|
3301 | Unstable operation > Generator output too low There is not enough power at the DC input of the inverter for stable operation. This may be caused by snow on the PV modules or insufficient irradiation. The inverter interrupts feed-in operation and can no longer connect to the utility grid. Corrective measures:
|
3302 | Unstable operation > Abort self-test There is not enough power at the DC input of the inverter for stable operation. This may be caused by snow on the PV modules or insufficient irradiation. The inverter interrupts feed-in operation and can no longer connect to the utility grid. Corrective measures:
|
3303 | Unstable operation > Data storage blocked There is not enough power at the DC input of the inverter for stable operation. This may be caused by snow on the PV modules or insufficient irradiation. The inverter interrupts feed-in operation and can no longer connect to the utility grid. Corrective measures:
|
3401 to 3402 | DC overvoltage > Disconnect PV array Overvoltage at the DC input. This can destroy the inverter. Corrective measures:
If the DC voltage is below the maximum input voltage of the inverter, reconnect the DC connectors to the inverter. If the DC voltage is above the maximum input voltage of the inverter, ensure that the PV array has been correctly rated or contact the installer of the PV array. |
3501 | Insulation resistance > Check generator The inverter has detected a ground fault in the PV array. Corrective measures:
|
3601 | High leakage current > Check PV array The leakage currents of the inverter and the PV array are too high. There is a ground fault, a residual current or a malfunction. The inverter interrupts feed-in operation immediately after exceeding a threshold and then automatically reconnects to the utility grid. If this process happens five times a day, the inverter disconnects from the utility grid and terminates feed-in. Corrective measures:
|
3701 | Residual current too high > Check PV array The inverter has detected a residual current due to temporary grounding of the PV array. Corrective measures:
|
3801 to 3802 | DC overcurrent > Check PV array Overcurrent at the DC input. The inverter briefly interrupts feed-in operation. Corrective measures:
|
3901 to 3902 | Waiting for DC start conditions > Start conditions not met The feed-in conditions for the utility grid are not yet fulfilled. Corrective measures:
|
4301 | Serial el.arc in String detected by AFCI mod. The inverter has detected an electric arc. The inverter interrupts grid feed-in and cannot connect to the utility grid. Corrective measures:
|
6001 to 6438 | Self-diagnosis > Device disturbance The cause must be determined by the Service. Corrective measures:
|
6501 to 6511 | Self-diagnosis > Device disturbance The inverter has switched off due to excessive temperature. Corrective measures:
|
6512 | Minimum operating temperature not reached The inverter will only recommence grid feed-in once the temperature has reached at least −25°C (−13°F). |
6603 to 6604 | Self-diagnosis > Overload The cause must be determined by the Service. Corrective measures:
|
6606 | Device fault The cause must be determined by the Service. Corrective measures:
|
6701 to 6702 | Communication failure The cause must be determined by the Service. Corrective measures:
|
6801 to 6802 | Self-diagnosis > Input A defective The cause must be determined by the Service. Corrective measures:
|
6901 to 6902 | Self-diagnosis > Input B defective The cause must be determined by the Service. Corrective measures:
|
7001 to 7002 | Fan sensor error permanently on The cause must be determined by the Service. Corrective measures:
|
7101 | SD memory card defective The SD memory card is not formatted. Corrective measures:
|
7105 | Parameter setting failed Parameters could not be set using the memory card. The inverter continues to feed in. Corrective measures:
|
7106 | Update file defective Update file on the memory card is defective. Corrective measures:
|
7102 | Parameter file not found or defective The parameter file was not found or is defective. The update failed. The inverter continues to feed in. Corrective measures:
|
7110 | No update file found No update file has been found. Corrective measures:
|
7201 to 7202 | Data stor. not poss. Internal error. The inverter continues to feed into the utility grid. Corrective measures:
|
7303 | Host computer update failed The cause must be determined by the Service. Corrective measures:
|
7305 | Update RS485I module failed Update of RS485i module failed. Corrective measures:
|
7311 | Update language table failed Updating the language table failed. Corrective measures:
|
7316 | Update Speedwire module failed Updating the Speedwire module failed. Corrective measures:
|
7324 | Wait for update conditions The inverter has successfully completed the update and is waiting for sufficient DC irradiation. |
7326 | Webconnect update failed Update of Webconnect module failed. Corrective measures:
|
7508 | External fan fault > Replace fan One of the fans is blocked. Corrective measures:
|
7701 to 7703 | Self-diagnosis > Device disturbance The cause must be determined by the Service. Corrective measures:
|
8001 | Derating occurred The inverter has reduced its power output for more than ten minutes due to excessive temperature. Corrective measures:
|
8101 to 8104 | Communication failure The cause must be determined by the Service. Corrective measures:
|
8204 | AFCI self-test failed The cause must be determined by the Service. Corrective measures:
|
8206 | Electr. arc detected > Please confirm by tapping The inverter has detected an electric arc and was recommissioned after a disconnection. By tapping, you are confirming that you have repaired any possible damage to PV modules, cables or plugs in the PV system. Corrective measures:
|
8708 | Timeout in communication for active power limitation Communication to the system control absent. Depending on the fall-back setting, either the last received values will be retained or the active power will be limited to the set percentage value of the inverter nominal power. Corrective measures:
|
8709 | Timeout in communication for reactive power setpoint Communication to the system control absent. Depending on the fall-back setting, either the last received values will be retained or the reactive power will be set to the set value. Corrective measures:
|
8710 | Timeout in communication for cos phi setpoint Communication to the system control absent. Depending on the fall-back setting, either the last received values will be retained or the displacement power factor will be set to the set value. Corrective measures:
|
9002 | SMA Grid Guard code invalid The SMA Grid Guard code entered is incorrect. The operating parameters are still protected and cannot be changed. Corrective measures:
|
9003 | Grid parameters locked The parameters are now locked. You cannot change the parameters. Corrective measures:
|
9005 | Changing of grid parameters not possible > Ensure DC supply PV power is too low for setting the country data set. As soon as sufficient irradiation is available, the inverter assumes the setting automatically. |
27301 | Update communication The inverter is updating the communication component. |
27302 | Update main CPU The inverter is updating the inverter component. |
27312 | Update completed The inverter has successfully completed the update. |
27103 | Set parameter The inverter is setting the parameters. |
27104 | Parameters set successfully The inverter is setting the parameters. |
27107 | Update file OK The update file found is valid. |
27108 | SD memory card is read The inverter is currently reading the SD memory card. |
27109 | No new update SD memory card There are no update files relevant for this inverter on the SD memory card or the available update has already been carried out. |
27304 | Update RS485i module The inverter is updating the 485 Data Module. |
27317 | Update Speedwire The inverter is updating the Speedwire data module. |
27325 | Webconnect update The inverter is updating the Webconnect Data Module. |
27310 | Upd. language table The inverter is updating the Webconnect Data Module. |
28205 | AFCI self-test successful The inverter has successfully performed the arc fault detection self-test. |
29001 | Grid Guard code valid The entered SMA Grid Guard code is valid. Protected parameters have now been unlocked and you can adjust the parameters. The parameters will be automatically locked again after 10 feed-in hours. |
29004 | Grid parameter unchanged Changing the grid parameters is not possible. |