Event Messages


Event number

Message, cause and corrective measures

101 to 103

Grid incident

The grid voltage or grid impedance at the connection point of the inverter is too high. The inverter has disconnected from the utility grid.

Corrective measures:

  • Check whether the grid voltage at the connection point of the inverter is permanently in the permissible range.

    If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must agree with an adjustment of the voltage at the feed-in point or with a change of the monitored operating limits.

    If the grid voltage is permanently within the permissible range and this message is still displayed, contact the Service.

202 to 203

Grid incident

The utility grid has been disconnected, the AC cable is damaged or the grid voltage at the connection point of the inverter is too low. The inverter has disconnected from the utility grid.

Corrective measures:

  1. Ensure that the circuit breaker is switched on.
  2. Make sure that the AC cable is not damaged.
  3. Make sure that the AC cable is correctly connected.
  4. Check whether the grid voltage at the connection point of the inverter is permanently in the permissible range.
  5. If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must agree with an adjustment of the voltage at the feed-in point or with a change of the monitored operating limits.

    If the grid voltage is permanently within the permissible range and this message is still displayed, contact the Service.

301

Grid incident

The ten-minute average value of the grid voltage is no longer within the permissible range. The grid voltage or grid impedance at the connection point is too high. The inverter disconnects from the utility grid to maintain power quality.

Corrective measures:

  • Check whether the grid voltage at the connection point of the inverter is permanently in the permissible range.

    If the grid voltage is outside the permissible range due to local grid conditions, contact the grid operator. The grid operator must agree with an adjustment of the voltage at the feed-in point or with a change of the monitored operating limits.

    If the grid voltage is permanently within the permissible range and this message is still displayed, contact the Service.

401

Grid incident

The inverter is no longer in grid-parallel operation. The inverter has stopped feeding into the utility grid.

Corrective measures:

  • Check the grid connection for significant short-term frequency fluctuations.

404

Grid incident

The inverter is no longer in grid-parallel operation. The inverter has stopped feeding into the utility grid.

Corrective measures:

  • Check the grid connection for significant short-term frequency fluctuations.

501

Grid incident

The power frequency is not within the permissible range. The inverter has disconnected from the utility grid.

Corrective measures:

  • If possible, check the power frequency and observe how often fluctuations occur.

    If fluctuations occur frequently and this message is displayed often, contact the grid operator. The grid operator must approve changes to the operating parameters of the inverter.

    If the grid operator gives his approval, discuss any changes to the operating parameters with the Service.

601

Grid incident

The inverter has detected an excessively high proportion of direct current in the grid current.

Corrective measures:

  1. Check the grid connection for direct current.
  2. If this message is displayed frequently, contact the grid operator and check whether the monitoring threshold on the inverter can be raised.

701

Frequency not permitted > Check parameter

The power frequency is not within the permissible range. The inverter has disconnected from the utility grid.

Corrective measures:

  • If possible, check the power frequency and observe how often fluctuations occur.

    If fluctuations occur frequently and this message is displayed often, contact the grid operator. The grid operator must approve changes to the operating parameters of the inverter.

    If the grid operator gives his approval, discuss any changes to the operating parameters with the Service.

901

Grounding connection missing > Check connection

The grounding conductor is not correctly connected.

Corrective measures:

1302

Waiting for grid voltage > Installation failure grid connection > Check grid and fuses

The inverter has detected an error in the AC cabling. The inverter cannot connect to the utility grid.

Corrective measures:

  1. Ensure that the AC connection is correct AC Connection).
  2. Ensure that the country data set has been configured correctly. Select the parameter Set country standard or CntrySet and check its value.

1501

Reconnection fault grid

The changed country data set or the value of a parameter you have set does not correspond to the local requirements. The inverter cannot connect to the utility grid.

Corrective measures:

  • Ensure that the country data set has been configured correctly. Select the parameter Set country standard or CntrySet and check its value.

3301

Unstable operation > Generator output too low

There is not enough power at the DC input of the inverter for stable operation. This may be caused by snow on the PV modules or insufficient irradiation. The inverter interrupts feed-in operation and can no longer connect to the utility grid.

Corrective measures:

  1. Wait for higher irradiation.
  2. If this message is displayed frequently, ensure that the PV array has been correctly rated and wired.

3302

Unstable operation > Abort self-test

There is not enough power at the DC input of the inverter for stable operation. This may be caused by snow on the PV modules or insufficient irradiation. The inverter interrupts feed-in operation and can no longer connect to the utility grid.

Corrective measures:

  1. If irradiation is too low, wait for it to increase.
  2. If this message is displayed frequently, ensure that the PV array has been correctly rated and wired.

3303

Unstable operation > Data storage blocked

There is not enough power at the DC input of the inverter for stable operation. This may be caused by snow on the PV modules or insufficient irradiation. The inverter interrupts feed-in operation and can no longer connect to the utility grid.

Corrective measures:

  1. Wait for higher irradiation.
  2. If this message is displayed frequently, ensure that the PV array has been correctly rated and wired.

3401 to 3402

DC overvoltage > Disconnect PV array

Overvoltage at the DC input. This can destroy the inverter.

Corrective measures:

  1. Immediately disconnect the inverter from all voltage sources Disconnecting the Inverter from Voltage Sources).
  2. Check whether the DC voltage is below the maximum input voltage of the inverter.
  3. If the DC voltage is below the maximum input voltage of the inverter, reconnect the DC connectors to the inverter.

    If the DC voltage is above the maximum input voltage of the inverter, ensure that the PV array has been correctly rated or contact the installer of the PV array.

  4. If this message is repeated frequently, contact the Service.

3501

Insulation resistance > Check generator

The inverter has detected a ground fault in the PV array.

Corrective measures:

3601

High leakage current > Check PV array

The leakage currents of the inverter and the PV array are too high. There is a ground fault, a residual current or a malfunction.

The inverter interrupts feed-in operation immediately after exceeding a threshold and then automatically reconnects to the utility grid. If this process happens five times a day, the inverter disconnects from the utility grid and terminates feed-in.

Corrective measures:

3701

Residual current too high > Check PV array

The inverter has detected a residual current due to temporary grounding of the PV array.

Corrective measures:

3801 to 3802

DC overcurrent > Check PV array

Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.

Corrective measures:

  • If this message is displayed frequently, ensure that the PV array has been correctly rated and wired.

3901 to 3902

Waiting for DC start conditions > Start conditions not met

The feed-in conditions for the utility grid are not yet fulfilled.

Corrective measures:

  1. Wait for higher irradiation.
  2. If this message is displayed frequently in the morning, increase the voltage limit for starting grid feed-in. Change the parameter minimum voltage input or A.VStr, B.VStr.
  3. If this message is displayed frequently with medium irradiation, ensure that the PV array is correctly rated.

4301

Serial el.arc in String detected by AFCI mod.

The inverter has detected an electric arc. The inverter interrupts grid feed-in and cannot connect to the utility grid.

Corrective measures:

6001 to 6438

Self-diagnosis > Device disturbance

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

6501 to 6511

Self-diagnosis > Device disturbance

The inverter has switched off due to excessive temperature.

Corrective measures:

  1. Clean the fans Cleaning the Fans).
  2. Ensure that the inverter has sufficient ventilation.

6512

Minimum operating temperature not reached

The inverter will only recommence grid feed-in once the temperature has reached at least −25°C (−13°F).

6603 to 6604

Self-diagnosis > Overload

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

6606

Device fault

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

6701 to 6702

Communication failure

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

6801 to 6802

Self-diagnosis > Input A defective

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

6901 to 6902

Self-diagnosis > Input B defective

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

7001 to 7002

Fan sensor error permanently on

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

7101

SD memory card defective

The SD memory card is not formatted.

Corrective measures:

  • Re-format the SD memory card.

  • Re-save the files to the SD memory card.

7105

Parameter setting failed

Parameters could not be set using the memory card. The inverter continues to feed in.

Corrective measures:

  • Ensure that the parameters are set correctly.

  • Ensure that you have an SMA Grid Guard code.

7106

Update file defective

Update file on the memory card is defective.

Corrective measures:

  • Reformat the memory card.

  • Re-save the files to the memory card.

7102

Parameter file not found or defective

The parameter file was not found or is defective. The update failed. The inverter continues to feed in.

Corrective measures:

  • Copy the parameter file to the correct folder again.

7110

No update file found

No update file has been found.

Corrective measures:

  • Copy the update file to the memory card folder. Select the folder \UPDATE.

7201 to 7202

Data stor. not poss.

Internal error. The inverter continues to feed into the utility grid.

Corrective measures:

  • Contact the Service.

7303

Host computer update failed

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

7305

Update RS485I module failed

Update of RS485i module failed.

Corrective measures:

  • Retry update.

  • If the error recurs, contact the Service.

7311

Update language table failed

Updating the language table failed.

Corrective measures:

  • Retry update.

  • If the error recurs, contact the Service.

7316

Update Speedwire module failed

Updating the Speedwire module failed.

Corrective measures:

  • Retry update.

  • If the error recurs, contact the Service.

7324

Wait for update conditions

The inverter has successfully completed the update and is waiting for sufficient DC irradiation.

7326

Webconnect update failed

Update of Webconnect module failed.

Corrective measures:

  • Retry update.

  • If the error recurs, contact the Service.

7508

External fan fault > Replace fan

One of the fans is blocked.

Corrective measures:

7701 to 7703

Self-diagnosis > Device disturbance

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

8001

Derating occurred

The inverter has reduced its power output for more than ten minutes due to excessive temperature.

Corrective measures:

  • Clean the cooling fins on the rear of the enclosure and the air ducts on the top using a soft brush.

  • Clean the fans Cleaning the Fans).

  • Ensure that the inverter has sufficient ventilation.

8101 to 8104

Communication failure

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

8204

AFCI self-test failed

The cause must be determined by the Service.

Corrective measures:

  • Contact the Service.

8206

Electr. arc detected > Please confirm by tapping

The inverter has detected an electric arc and was recommissioned after a disconnection. By tapping, you are confirming that you have repaired any possible damage to PV modules, cables or plugs in the PV system.

Corrective measures:

  • Tap on the enclosure lid within ten seconds of the message appearing in order to recommission the inverter.

8708

Timeout in communication for active power limitation

Communication to the system control absent. Depending on the fall-back setting, either the last received values will be retained or the active power will be limited to the set percentage value of the inverter nominal power.

Corrective measures:

  • Ensure that the connection to the system manager (e.g. Sunny Home Manager) is intact and that no cables are damaged or that no plugs have been pulled.

8709

Timeout in communication for reactive power setpoint

Communication to the system control absent. Depending on the fall-back setting, either the last received values will be retained or the reactive power will be set to the set value.

Corrective measures:

  • Ensure that the connection to the system manager (e.g. Sunny Home Manager) is intact and that no cables are damaged or that no plugs have been pulled.

8710

Timeout in communication for cos phi setpoint

Communication to the system control absent. Depending on the fall-back setting, either the last received values will be retained or the displacement power factor will be set to the set value.

Corrective measures:

  • Ensure that the connection to the system manager (e.g. Sunny Home Manager) is intact and that no cables are damaged or that no plugs have been pulled.

9002

SMA Grid Guard code invalid

The SMA Grid Guard code entered is incorrect. The operating parameters are still protected and cannot be changed.

Corrective measures:

  • Enter the correct SMA Grid Guard code.

9003

Grid parameters locked

The parameters are now locked. You cannot change the parameters.

Corrective measures:

  • Unlock the parameters with the SMA Grid Guard code.

9005

Changing of grid parameters not possible > Ensure DC supply

PV power is too low for setting the country data set. As soon as sufficient irradiation is available, the inverter assumes the setting automatically.

27301

Update communication

The inverter is updating the communication component.

27302

Update main CPU

The inverter is updating the inverter component.

27312

Update completed

The inverter has successfully completed the update.

27103

Set parameter

The inverter is setting the parameters.

27104

Parameters set successfully

The inverter is setting the parameters.

27107

Update file OK

The update file found is valid.

27108

SD memory card is read

The inverter is currently reading the SD memory card.

27109

No new update SD memory card

There are no update files relevant for this inverter on the SD memory card or the available update has already been carried out.

27304

Update RS485i module

The inverter is updating the 485 Data Module.

27317

Update Speedwire

The inverter is updating the Speedwire data module.

27325

Webconnect update

The inverter is updating the Webconnect Data Module.

27310

Upd. language table

The inverter is updating the Webconnect Data Module.

28205

AFCI self-test successful

The inverter has successfully performed the arc fault detection self-test.

29001

Grid Guard code valid

The entered SMA Grid Guard code is valid. Protected parameters have now been unlocked and you can adjust the parameters. The parameters will be automatically locked again after 10 feed-in hours.

29004

Grid parameter unchanged

Changing the grid parameters is not possible.