Requirements for the DC Connection
Requirements for the PV modules per input:
- All PV modules must be of the same type.
- All PV modules must be aligned and tilted identically.
- On the coldest day based on statistical records, the open-circuit voltage of the PV array must never exceed the maximum input voltage of the inverter.
- The same number of series-connected PV modules must be connected to each string.
- The thresholds for the input voltage and the input current of the inverter must be adhered to ( > Technical Data).
- The maximum input current per string must be maintained ( > Technical Data).
Additionally required material (not included in the scope of delivery):
- Depending on the number of strings, one or two conduits made of metal: 25.4 mm (1 in)
- Depending on the number of conduits, one or two rain-tight conduit fittings for wet locations complying with UL 25.4 mm (1 in)
- For closing unused enclosure openings for the DC connection: UL-listed type 3R filler plugs
Cable requirements:
- The DC cables must be approved for temperatures of over +90°C (+194°F).
- The maximum cable length subject to conductor cross-section must be observed.
- Conductor type: copper wire
- Only use solid wire or stranded wires.
- Conductor cross-section: 10 mm² to 35 mm² (8 AWG to 2 AWG)
- The DC cables must be sized in accordance with the installation requirements applicable on site.