Mount the product.


Qualified person

DANGER

Danger to life due to electric shock when live cables are touched

High voltages are present on the AC and DC cables. Touching live cables results in death or lethal injuries due to electric shock.

  1. Do not touch non-insulated parts or cables.
  2. Disconnect the AC circuit breaker and secure it against reconnection.
  3. Disconnect the PV array from the inverter via an external DC load-break switch (e.g. via a PV junction including a load-break switch). Switch off and secure the DC load-break switch against reconnection.
  4. Ensure that all cables to be connected are de-energized.
  5. Wear suitable personal protective equipment for all work on the product.

CAUTION

Risk of injury due to weight of product

Injuries may result if the product is lifted incorrectly or dropped while being transported or mounted.

  1. Transport and lift the product carefully. Take the weight of the product into account.
  2. Wear suitable personal protective equipment for all work on the product.
  3. Transport the product using the carrying handles or hoist. Take the weight of the product into account.
  4. Use all carrying handles provided during transport with carrying handles.
  5. Do not use the carrying handles as attachment points for hoist equipment (e.g. straps, ropes, chains). Insert eye bolts into threads provided on top of the product to attach the hoist system.

Requirement:

  • Mounting and connection are prepared .

Procedure:

    4920525964
  1. Screw the transport handles as far as they will go into the tapped holes on the right- and left-hand side until they lie flush with the enclosure. When doing so, ensure that the transport handles are screwed into the tapped holes so that they are perfectly straight. If the transport handles are not screwed in straight, this can make it more difficult or even impossible to unscrew them later on and can damage the tapped holes to the extent that transport handles can no longer be screwed into them.
  2. 4920526348
  3. Insert a screwdriver into the holes in the transport handle and turn the screwdriver through 90°. This ensures that the transport handles are securely tightened.
  4. If the product should be hung into the mounting bracket with the help of a hoist, screw the eye bolts into the threads on the top of the product and attach the hoist to them. The hoist must be suitable for the weight of the product.
  5. 11114203788
  6. Remove the cover from the enclosure lid.
  7. 11114204172
  8. Unscrew the screw on the enclosure lid (hex socket, AF8) and remove the enclosure lid.
  9. Set the cover, screw with seal, washer with seal and enclosure lid aside and store safely.
  10. 11209431052
  11. Hook the product into the mounting brackets. To do this, guide the product over the cables and the connecting plate so that the cables protrude through the opening into the product and the connecting plate sits under the opening. The bracket must protrude through the upper opening.
  12. Align the cables according to the corresponding terminals and shorten the cables if necessary.
  13. 4144033932
  14. Secure the product with one screw each on the right and left on the mounting bracket (M8x16, TX40, 12 Nm ± 2 Nm).
  15. 4920526732
  16. Remove all 4 transport handles from the tapped holes. If necessary, insert a screwdriver into the holes on the transport handle and use the screwdriver to remove the transport handle.
  17. 5507826828
  18. Fasten the connecting plate to the enclosure using three screws (M8x70, TX40, torque: 8 Nm ± 0.5 Nm).