Carry out the configuration manually
Qualified person
You can configure the inverter manually by setting the desired parameters.
Requirements:
You are logged in as Installer, and the user interface is open on the Configuring the Inverter page.
When configuring after completion of the first ten feed-in hours, the SMA Grid Guard code must be available in order to change the grid-relevant parameters. You can request the SMA Grid Guard code via the Online Service Center.
Procedure:
- Select the configuration option Manual Configuration.
- The Device Parameters menu on the user interface will open and all available parameter groups of the inverter will be displayed.
- Click on [Edit parameters].
- Select the desired parameter group.
- All available parameters of the parameter group will be displayed.
- Set the desired parameters.
- Select [Save all].
- The inverter parameters are set.