Configuring the active power mode for systems with external setpoint


Qualified person

Requirement:

  • Installation assistant has been started.

Procedure:

  1. Select [Save and continue] after each step up until the step Grid management service.
  2. In the tab Active power mode set the switch Active power setpoint to [On].
  3. In the drop-down list Operating mode active power setpoint, select the entry External setpoint.
  4. In the drop-down list Fallback behavior, select the entry Apply fallback values.
  5. In the Fallback value of maximum active power field, enter the value to which the product should limit its nominal power if communication to the higher-level control unit fails after the timeout time has elapsed.
  6. In the Timeout field, enter the time that the product should wait until it limits its nominal power to the set fallback value.