AC Output
SHP 100-JP-21 | SHP 143-JP-21 | |
---|---|---|
Rated power at nominal AC voltage, 50 Hz | 100 kW | 143 kW |
Maximum apparent AC power | 100 kVA | 143 kVA |
Rated grid voltage, 50 Hz | 420 V | 550 V |
Rated grid voltage, 60 Hz | 440 V | 550 V |
AC voltage range, 420 V | 336 V to 485 V | - |
AC voltage range, 440 V | 352 V to 506 V | - |
AC voltage range, 550 V | - | 480 V to 600 V |
Nominal AC current at 420 V nominal AC voltage | 138 A | - |
Nominal AC current at 440 V nominal AC voltage | 132 A | - |
Nominal AC current at 550 V nominal AC voltage | - | 151 A |
Maximum output current | 151 A | 151 A |
Maximum residual output current | 662.8 A | 662.8 A |
Duration of the maximum residual output current | 446.7 ms | 446.7 ms |
Total harmonic distortion | < 0.5 % | < 0.5 % |
Inrush current | < 10% of the nominal AC current for a maximum of 10 ms | < 10% of the nominal AC current for a maximum of 10 ms |
Rated grid frequency | 50 Hz | 50 Hz |
AC grid frequency | 50 Hz / 60 Hz | 50 Hz / 60 Hz |
Operating range at AC grid frequency 50 Hz | 44 Hz to 55 Hz | 44 Hz to 55 Hz |
Operating range at AC grid frequency 60 Hz | 54 Hz to 66 Hz | 54 Hz to 66 Hz |
Power factor at rated power | 1 | 1 |
Displacement power factor, adjustable | 0.0 overexcited to 0.0 underexcited | 0.0 overexcited to 0.0 underexcited |
Feed-in phases | 3 | 3 |
Connection phases | 3 grounding conductor | 3 grounding conductor |
Overvoltage category as per IEC 62109-1 | III | III |