Configuring the RS485 Interface
Requirements:
The inverter must be configured as a subordinate device.
The SMA RS485 module (MD.485-41) must be installed in the inverter (see SMA RS485module manual).
The user interface for the subordinate device must be open and you must be logged in as an installer or administrator.
Procedure:
- Select the menu Configuration.
- Select the menu item External communication.
- Under Data-1 Server select the button [Carry out initial configuration].
- Use the slider to activate the data-1 server.
- Select the displayed port.
- Set the baud rate (1200 baud or 19200 baud).
- The RS485 interface is active and configured.