Assembling the DC Connectors


Qualified person

For connection to the inverter, all PV module connection cables must be fitted with the DC connectors provided. Assemble the DC connectors as described in the following. The procedure is identical for both connectors (+ and -). The graphics for the procedure are shown for only the positive connector as an example. Pay attention to the correct polarity when assembling the DC connectors. The DC connectors are marked with the symbols "+" and "-".

NOTICE

Destruction of the inverter due to overvoltage

If the open-circuit voltage of the PV modules exceeds the maximum input voltage of the inverter, the inverter can be destroyed due to overvoltage.

  1. If the open-circuit voltage of the PV modules exceeds the maximum input voltage of the inverter, do not connect any strings to the inverter and check the design of the PV system.

Procedure:

  1. Strip approx. 15 mm of the cable insulation.
  2. 11635247372
  3. Insert the stripped cable into the DC connector up to the stop. When doing so, ensure that the stripped cable and the DC connector are of the same polarity.
  4. 11635247756
  5. Press the clamping bracket down until it audibly snaps into place.
  6. 11635248140
  7. The stranded wire can be seen inside the clamping bracket chamber.
  8. If the stranded wire is not visible in the chamber, the cable is not correctly inserted and the connector must be reassembled. To do this, the cable must be removed from the connector.
  9. 11635248524
  10. To take out the cable, loosen the clamping bracket. To do so, insert a screwdriver (blade width: 3.5 mm) into the clamping bracket and pry the clamping bracket open.
  11. Remove the cable and go back to step 2.
  12. 11635248908
  13. Push the swivel nut up to the thread and tighten (torque: 2 Nm).