Sunny Tripower 8000TL / 9000TL / 10000TL
DC Input
STP 8000TL-20 |
STP 9000TL-20 |
STP 10000TL-20 | |
---|---|---|---|
Maximum DC power at cos φ = 1 |
8200 W |
9225 W |
10250 W |
Maximum input voltage |
1000 V |
1000 V |
1000 V |
MPP voltage range |
330 V to 800 V |
370 V to 800 V |
370 V to 800 V |
Rated input voltage |
580 V |
580 V |
580 V |
Minimum usable input voltage |
150 V |
150 V |
150 V |
Initial input voltage |
188 V |
188 V |
188 V |
Maximum input current, input A |
15 A |
15 A |
18 A |
Maximum input current, input B |
10 A |
10 A |
10 A |
Maximum input current per string, input A |
15 A |
15 A |
18 A |
Maximum input current per string, input B |
10 A |
10 A |
10 A |
Maximum short-circuit current, input A* |
25 A |
25 A |
25 A |
Maximum short-circuit current, input B* |
15 A |
15 A |
15 A |
Maximum reverse current from the inverter in the system for max. 1 ms |
0 A |
0 A |
0 A |
Number of independent MPP inputs |
2 |
2 |
2 |
Strings per MPP input |
2 |
2 |
2 |
Overvoltage category in accordance with IEC 60664-1 |
II |
II |
II |
* In accordance with IEC 62109-2: ISC PV
AC Output
STP 8000TL-20 |
STP 9000TL-20 |
STP 10000TL-20 | |
---|---|---|---|
Rated power at 230 V, 50 Hz |
8000 W |
9000 W |
10000 W |
Maximum apparent AC power at cos φ = 1 |
8000 VA |
9000 VA |
10000 VA |
Rated grid voltage |
∼3/N/PE, 230 V / 400 V |
∼3/N/PE, 230 V / 400 V |
∼3/N/PE, 230 V / 400 V |
AC voltage range* |
160 V to 280 V |
160 V to 280 V |
160 V to 280 V |
Nominal AC current at 220 V |
11.6 A |
13.1 A |
14.5 A |
Nominal AC current at 230 V |
11.6 A |
13.1 A |
14.5 A |
Nominal AC current at 240 V |
11.1 A |
12.5 A |
13.9 A |
Maximum output current |
11.6 A |
13.1 A |
14.5 A |
Total harmonic distortion of the output current with total harmonic distortion of the AC voltage < 2%, and AC power > 50% of the rated power |
≤3 % |
≤3 % |
≤3 % |
Maximum output current under fault conditions |
20 A |
22 A |
25 A |
Rated power frequency |
50 Hz |
50 Hz |
50 Hz |
AC power frequency* |
50 Hz / 60 Hz |
50 Hz / 60 Hz |
50 Hz / 60 Hz |
Operating range at AC power frequency 50 Hz |
45.5 Hz to 54.5 Hz |
45.5 Hz to 54.5 Hz |
45.5 Hz to 54.5 Hz |
Operating range at AC power frequency 60 Hz |
55.5 Hz to 64.5 Hz |
55.5 Hz to 64.5 Hz |
55.5 Hz to 64.5 Hz |
Displacement power factor cos φ, adjustable |
0.8 underexcited to 1 to 0.8 overexcited |
0.8 underexcited to 1 to 0.8 overexcited |
0.8 underexcited to 1 to 0.8 overexcited |
Feed-in phases |
3 |
3 |
3 |
Phase connection |
3 |
3 |
3 |
Overvoltage category in accordance with IEC 60664-1 |
III |
III |
III |
* depending on the configured country data set
Efficiency
STP 8000TL-20 |
STP 9000TL-20 |
STP 10000TL-20 | |
---|---|---|---|
Maximum efficiency, ηmax |
98 % |
98 % |
98 % |
European weighted efficiency, ηEU |
97.6 % |
97.6 % |
97.6 % |