Requirements for the DC Connection
Requirements for the PV modules per input:
- All PV modules must be of the same type.
- All PV modules must be aligned and tilted identically.
- On the coldest day based on statistical records, the open-circuit voltage of the PV array must never exceed the maximum input voltage of the inverter.
- The same number of series-connected PV modules must be connected to each string.
- The maximum input current per string must be maintained and must not exceed the through-fault current of the DC connectors ( > Technical Data).
- The thresholds for the input voltage and the input current of the inverter must be adhered to ( > Technical Data).
- The positive connection cables of the PV modules must be fitted with the positive DC connectors (for information on assembling DC connectors, see the DC connector installation manual).
- The negative connection cables of the PV modules must be fitted with the negative DC connectors (for information on assembling DC connectors, see the DC connector installation manual).

Use of Y adapters for parallel connection of strings
The Y adapters must not be used to interrupt the DC circuit.
- Do not use the Y adapters in the immediate vicinity of the inverter. The adapters must not be visible or freely accessible.
- In order to interrupt the DC circuit, always disconnect the inverter as described in this document ( > Disconnecting the Inverter from Voltage Sources).