Configuring the Country Data Set


Qualified person

Set the country data set appropriate for your country or purpose within the first ten feed-in hours via the rotary switches in the inverter. After the first ten feed-in hours, the country data set can only be changed by means of a communication product.

A display language is assigned to every country data set. If the display language of the country data set does not match the required language, you can change it after commissioning Changing the Display Language).

Procedure:

  1. Determine the rotary switch position for your country and purpose. Call up the Technical Information "Overview of the Rotary Switch Settings" at www.SMA-Solar.com.
  2. DANGER

    Danger to life due to high voltages

    1. Ensure that the inverter is disconnected from all voltage sources and that the enclosure lid is removed Disconnecting the Inverter from Voltage Sources).
    693568268
  3. Set the rotary switches A and B to the required position using a flat-blade screwdriver (blade width: 2.5 mm).
  • The inverter will adopt the setting after commissioning. This can take up to five minutes.