AC Output


STPS30-20

STPS50-20

Rated power at nominal voltage

30000 W

50000 W

Maximum apparent power

30000 VA

50000 VA

Maximum reactive power

30000 var

50000 var

Nominal grid voltage

400 V

400 V

Voltage range1)

340 V to 477 V

340 V to 477 V

Rated current per line conductor

43.3 A

72.2 A

Maximum current per line conductor

45.6 A

75.5 A

Rated grid frequency1)

50 Hz / 60 Hz

50 Hz / 60 Hz

Operating range at grid frequency 50 Hz1)

44 Hz to 55 Hz

44 Hz to 55 Hz

Operating range at grid frequency 60 Hz1)

55 Hz to 66 Hz

55 Hz to 66 Hz

Required minimum grid short-circuit current

3 kA

3 kA

Permissible maximum grid short-circuit current

50 kA

50 kA

Power factor at rated power

1

1

Displacement power factor, adjustable

0 overexcited to 0 underexcited

0 overexcited to 0 underexcited

Charging and discharging phases

3

3

Connection phases

3-N-PE

3-N-PE

Protection class (according to IEC 62109-1)

I

I

Overvoltage category as per IEC 60664-1 for AC

III

III

Connectable conductor cross-section

16 mm² to 95 mm²

16 mm² to 95 mm²

External diameter of the connection cables

35 mm to 48 mm

35 mm to 48 mm

Grid configuration

TT / TN-C / TN-S / TN-C-S

TT / TN-C / TN-S / TN-C-S

1) Depending on the configured country data set