Event Messages
Event number | Message, cause and corrective measures |
---|---|
101 102 103 105 202 203 206 |
Grid incident The grid voltage or grid impedance at the connection point of the inverter is too high. The inverter has disconnected from the utility grid. Corrective measures:
|
301 |
Grid incident The ten-minute average value of the grid voltage is no longer within the permissible range. The grid voltage or grid impedance at the connection point is too high. The inverter disconnects from the utility grid to maintain power quality. Corrective measures:
|
302 |
Active power limit AC voltage The inverter has reduced its power due to a too-high grid voltage to ensure grid stability. Corrective measures:
|
401 404 |
Grid incident The inverter has disconnected from the utility grid. A stand-alone grid or a very large change in the grid frequency was detected. Corrective measures:
|
501 |
Grid incident The grid frequency is not within the permissible range. The inverter has disconnected from the utility grid. Corrective measures:
|
507 |
Active power limit AC frequency The inverter has reduced its power due to a too-high grid frequency to ensure grid stability. Corrective measures:
|
601 |
Grid incident The inverter has detected an excessively high proportion of direct current in the grid current. Corrective measures:
|
701 |
Frequency not permitted > Check parameter The grid frequency is not within the permissible range. The inverter has disconnected from the utility grid. Corrective measures:
|
1302 |
Waiting for grid voltage > Installation failure grid connection > Check grid and fuses L is not connected. Corrective measures:
|
1501 |
Reconnection fault grid The changed country data set or the value of a parameter you have set does not correspond to the local requirements. The inverter cannot connect to the utility grid. Corrective measures:
|
3302 3303 |
Unstable operation There is not enough power at the DC input of the inverter for stable operation. The inverter cannot connect to the utility grid. Corrective measures:
|
3401 |
DC overvoltage > Disconnect PV array Overvoltage at the DC input. This can destroy the inverter. This message is signalized additionally by rapid flashing of the LEDs. Corrective measures:
|
3501 |
Insulation failure > Check PV array The inverter has detected a ground fault in the PV array. Corrective measures:
|
3601 |
High leakage current > Check PV array The leakage current of the inverter and the PV array is too high. There is a ground fault, a residual current or a malfunction. The inverter interrupts feed-in operation immediately after exceeding a threshold. When the fault is eliminated, the inverter automatically reconnects to the utility grid. Corrective measures:
|
3701 |
Residual current too high > Check PV array The inverter has detected a residual current through brief grounding of the PV array. Corrective measures:
|
3901 3902 |
Waiting for DC start conditions > Start conditions not met The feed-in conditions for the utility grid are not yet fulfilled. Corrective measures:
|
6001-6438 |
Self-diagnosis > Device disturbance The cause must be determined by the Service. Corrective measures:
|
6501 6502 |
Self-diagnosis > Overtemperature The inverter has switched off due to excessive temperature. Corrective measures:
|
6511 |
Overtemperature An overtemperature has been detected in the choke area. Corrective measures:
|
6512 | Minimum operating temperature not reached The inverter will only recommence grid feed-in once the temperature has reached at least −25°C. |
6701 6702 |
Communication failure Error in the communication processor, the inverter continues feeding in, however. The cause must be determined by the Service. Corrective measures:
|
7001 7002 7015 | Fault sensor interior temperature The cause must be determined by the Service. Corrective measures:
|
7102 |
Parameter file not found or defective The parameter file was not found or is defective. Loading the parameter file has failed. The inverter continues to feed in. Corrective measures:
|
7106 | Update file defective The update file is defective. The update failed. The inverter continues to feed in. |
7112 | Update file successfully copied |
7113 | The memory card is full or write-protected |
7201 7202 | Data storage not possible |
7303 |
Host computer update failed The cause must be determined by the Service. Corrective measures:
|
7320 | The device was successfully updated The firmware update was completed successfully. |
7324 |
Wait for update conditions The testing of the update conditions was not successful. The firmware update package is not suitable for this inverter. Corrective measures:
|
7330 | Condition test failed The testing of the update conditions was not successful. The firmware update package is not suitable for this inverter. |
7331 | Update transport started Update file is being copied. |
7332 | Update transport successful Update file was copied successfully to the inverter's internal memory. |
7333 |
Update transport failed Update file could not be copied to the inverter's internal memory. Corrective measures:
|
7340 | Update communication failed |
7347 |
Incompatible file The configuration file is not suitable for this inverter. Corrective measures:
|
7348 |
Incorrect file format The configuration file is not of the required format or is damaged. Corrective measures:
|
7349 | Incorrect login rights for configuration file The user group logged in does not have the user rights necessary to be able to import a configuration. Corrective measures:
|
7350 | Transfer of a configuration file has started The configuration file is being transferred. |
7353 | Update time zone database The inverter is updating the time zone database. |
7619 |
Communication fault with meter unit > Check communication to meter The inverter is not receiving any data from the energy meter. Corrective measures:
|
7702 7703 |
Self-diagnosis > Device disturbance The cause must be determined by the Service. Corrective measures:
|
7801 |
Fault overvoltage protector One or more surge arresters have tripped or one or more surge arresters are not inserted correctly. Corrective measures:
|
8003 |
Active power limit temperature The inverter has reduced its power output for more than 10 minutes due to excessive temperature. Corrective measures:
|
8101 8102 8103 8104 |
Communication failure The cause must be determined by the Service. Corrective measures:
|
8708 |
Timeout in communication for active power limitation Communication to the system control absent. Depending on the fallback setting, either the last received values will be retained or the active power will be limited to the set percentage value of the inverter nominal power. Corrective measures:
|
8709 |
Timeout in communication for reactive power setpoint Communication to the system control absent. Corrective measures:
|
8710 |
Timeout in communication for cos phi setpoint Communication to the system control absent. Corrective measures:
|
9002 |
SMA Grid Guard code invalid The SMA Grid Guard code entered is incorrect. The operating parameters are still protected and cannot be changed. Corrective measures:
|
9003 | Grid parameters locked Changes to the grid parameters are now blocked. In order to be able to make changes to the grid parameters, from now on you must log in using the SMA Grid Guard code. |
9007 |
Abort self-test The self-test (Italy only) was terminated. Corrective measures:
|
9107 |
Self-diagnosis > Device disturbance The cause must be determined by the Service. Corrective measures:
|
10108 | Time adjusted / old time |
10109 | Time adjusted / new time |
10110 |
Time synchronization failed: [xx] No time information could be called up from the set NTP server. Corrective measures:
|
10118 | Parameter upload complete The configuration file was loaded successfully. |
10248 |
[Interface]: network busy The network is busy. Data exchange between the devices is not at an optimum and is greatly delayed. Corrective measures:
|
10249 |
[Interface]: network overloaded The network is overloaded. There is no data exchange between the devices. Corrective measures:
|
10250 |
[Interface]: package error rate [ok / high] The package error rate has changed. If the package error rate is high, the network is overloaded or the connection to the network switch or DHCP server (router) is impaired. Corrective measures if the package error rate is high:
|
10251 | [Interface]: communication status goes to [OK / Warning / Error / Not connected] The communication status to the network switch or DHCP server (router) has changed. An additional error message may be displayed. |
10252 |
[Interface]: communication disrupted There is no valid signal on the network line. Corrective measures:
|
10253 |
[Interface]: connection speed goes to [100 Mbit / 10 Mbit] The data transfer rate has changed. The cause for the status [10 Mbit] can be a defective plug, a defective cable or the pulling or plugging of the network connector. Corrective measures if the status is [10 Mbit]:
|
10254 |
[Interface]: duplex mode goes to [Full / Half] The duplex mode (data transfer mode) has changed. The cause for the status [Half] can be a defective plug, a defective cable or the pulling or plugging of the network connector. Corrective measures if the status is [Half]:
|
10255 |
[Interface]: Network load OK The network load has returned to a normal range after being busy. |
10282 | [User group]-Login via [protocol] locked After several incorrect login attempts, login has been blocked for a limited time. In this case, the User login will be blocked for 15 minutes, the Grid Guard login for 12 hours. Corrective measures:
|
10339 | Webconnect enabled |
10340 | Webconnect disabled |
10341 | Webconnect error: no connection |
10343 | Webconnect error: Default gateway not configured |
10344 | Webconnect error: DNS server not configured |
10345 | Webconnect error: No reply to DNS request |xx| |
10346 | Webconnect error: Unknown SIP proxy |xx| |
10347 | Webconnect error: Unknown STUN server |xx| |
10348 | Webconnect error: No reply to request to STUN server |
10349 | Webconnect error: No reply to SIP option packs |
10350 | Webconnect error: Registration rejected by SIP registrar |
10351 | Webconnect error: Unknown SIP registrar |xx| |
10352 | Webconnect error: Faulty communication |
10353 | Webconnect error: registration of the SIP registry has not responded |
10502 | Active power limit AC frequency |
10517 | Dynamic active power limitation started. |
10518 | Dynamic active power limitation terminated. |
10520 | Supplied power: |xx| W (permitted value: |xx| W) |
10521 | Active power was limited today for |xx| minutes. |
10525 | Inverter does not respond to active power limitation. |
10528 | System password of the connected device |xx| invalid |
10901 | Start self-test |xx| |
10902 | Current disconnection limit for voltage increase protection |xxx| V |
10903 | Current disconnection limit for voltage monitoring lower maximum threshold |xxx| V |
10904 | Current disconnection limit for voltage monitoring upper minimum threshold |xxx| V |
10905 | Current disconnection limit for voltage monitoring middle minimum threshold |xxx| V |
10906 | Current disconnection limit for frequency monitoring switchable maximum threshold |xxx| Hz |
10907 | Current disconnection limit for frequency monitoring switchable minimum threshold |xxx| Hz |
10908 | Current disconnection limit for frequency monitoring lower maximum threshold |xxx| Hz |
10909 | Current disconnection limit for frequency monitoring upper minimum threshold |xxx| Hz |
10910 | Measured disconnection threshold for the running test point |xxx| |xx| |
10911 | Standard value for the running test point |xxx| |xx| |
10912 | Measured disconnection time for the running test point |xx| s |
27103 | Set parameter The parameter changes are being adopted. |
27104 | Parameters set successfully The parameter changes were successfully adopted. |
27107 | Update file OK The update file found is valid. |
27301 | Update communication The inverter is updating the communication component. |
27302 | Update main CPU The inverter is updating the inverter component. |
27312 | Update completed The inverter has successfully completed the update. |
27329 | Condition test successful |
29001 | Inst. code valid The entered Grid Guard code is valid. Protected parameters have now been unlocked and you can adjust the parameters. The parameters will be automatically locked again after 10 feed-in hours. |
29004 | Grid parameter unchanged Changing the grid parameters is not possible. |