Disconnecting product connections


Qualified person

To decommission the product completely upon completion of its service life, first disconnect all connections from the product.

Procedure:

  1. Disconnect the product from voltage sources .
  2. 4903962124
  3. Remove the AC cable from the inverter. To do so, loosen the screws (AF8) and pull the cables out of the terminal.
  4. 4904063116
  5. Remove the protection elements against contact from the terminal lugs for the DC connection. To do so, unlock the side brackets.
  6. 4904063500
  7. Remove the DC cable connection. Loosen the hex nuts and remove the combined hexagon head screw (AF16).
  8. 11192444684
  9. Remove the network cables from the network ports.
  10. Remove all cable glands from the connecting plate. To do so, unscrew the counter nuts from inside and remove the cable glands from the opening.
  11. 5453376268
  12. Dismantle the connecting plate. To do so, unscrew the three screws (TX40).
  13. 11192143756
  14. Position the enclosure lid. The two guide pins on the enclosure lid must slide into the guide openings on the enclosure lid.
  15. 11192144140
  16. Ensure that the cover sits straight on the enclosure.
  17. 11192144524
  18. Hold the enclosure lid pressed against the enclosure and screw and tighten the screw (hex socket AF8, torque: 18 Nm).
  19. 11192144908
  20. Place the cover on the screw in the enclosure lid.
  21. Disassemble the product Disassembling the product).

    Also see: