Configuring the active power mode for systems with manual setpoint
Qualified person
Requirement:
Installation assistant has been started.
Procedure:
- Select [Save and continue] after each step up until the step Grid management service.
- In the tab Active power mode set the switch Grid connection point regulation to [On].
- Enter the total power of the PV array in the field Nominal system power.
- In the drop-down list Operating mode of active power limitation at the point of interconnection, select whether active power limitation is to be performed via a fixed specification in percent or in watts.
- In the field Set active power limit at the grid-connection point, enter the value to which the active power at the grid-connection point is to be limited. The value must be set to 0 for zero power output.
- Set the Active power setpoint to [On].
- You can manually specify the active power or have the active power controlled by the inverter.
- Manual preset: In the Operating mode active power setting drop-down list, select Manual setting in % or Manual setting in W.
- Manual preset: Enter the default value in the Active power field.
- Preset by inverter: In the drop-down list Operating mode active power setpoint, select the entry External setting.
- Preset by inverter: In the drop-down list Fallback behavior, select the entry Apply fallback values.
- Preset by inverter: In the drop-down list Grid disconnection for 0% active power setting select the entry No.