Sunny Boy 5.0 / 6.0


DC input

SB5.0-1AV-41

SB6.0-1AV-41

Maximum power of PV array

7500 Wp

9000 Wp

Maximum input voltage

600 V

600 V

MPP voltage range

125 V to 500 V

125 V to 500 V

Rated input voltage

365 V

365 V

Minimum input voltage

100 V

100 V

Initial input voltage

125 V

125 V

Maximum input current, input A

15 A

15 A

Maximum input current, input B

15 A

15 A

Maximum input current per string, input A

15 A

15 A

Maximum input current per string, input B

15 A

15 A

Maximum short-circuit current, input A*

20 A

20 A

Maximum short-circuit current, input B*

20 A

20 A

Maximum reverse current into the PV modules

0 A

0 A

Number of independent MPP inputs

2

2

Strings per MPP input

2

2

Surge category in accordance with IEC 60664-1

II

II

* In accordance with IEC 62109-2: ISC PV

AC Output

SB5.0-1AV-41

SB6.0-1AV-41

Rated power at 230 V, 50 Hz*

5000 W

6000 W

Maximum apparent AC power at cos φ = 1**

5000 VA

6000 VA

Rated grid voltage

230 V

230 V

Nominal AC voltage

220 V / 230 V / 240 V

220 V / 230 V / 240 V

AC voltage range***

180 V to 280 V

180 V to 280 V

Nominal AC current at 220 V

22.8 A

26.1 A

Nominal AC current at 230 V

22 A

26.1 A

Nominal AC current at 240 V

21 A

25 A

Maximum output current****

22.8 A

26.1 A

Total harmonic distortion of the output current with total harmonic distortion of the AC voltage <2%, and AC power >50% of the rated power

≤3 %

≤3 %

Maximum output current under fault conditions

29 A

29 A

Inrush current

< 20% of the nominal AC current for a maximum of 10 ms

< 20% of the nominal AC current for a maximum of 10 ms

Rated grid frequency

50 Hz

50 Hz

AC grid frequency***

50 Hz / 60 Hz

50 Hz / 60 Hz

Operating range at AC grid frequency 50 Hz

45 Hz to 55 Hz

45 Hz to 55 Hz

Operating range at AC grid frequency 60 Hz

55 Hz to 65 Hz

55 Hz to 65 Hz

Power factor at rated power

1

1

Displacement power factor cos φ, adjustable

0.8 overexcited to 1 to 0.8 underexcited

0.8 overexcited to 0.8 underexcited

Feed-in phases

1

1

Connection phases

1

1

Surge category in accordance with IEC 60664-1

III

III

* According to VDE-AR-N 4105, the rated power at 230 V, 50 Hz of the SB5.0-1AV-41 is 4600 W

** According to VDE-AR-N 4105, the rated power at 230 V, 50 Hz of the SB5.0-1AV-41 is 4600 VA

*** Depending on the configured country data set

**** According to AS 4777, the maximum output current is 21.7 A

Efficiency

SB5.0-1AV-41

SB6.0-1AV-41

Maximum efficiency, ηmax

97.0 %

97.0 %

European weighted efficiency, ηEU

96.5 %

96.5 %