Event 3908


Qualified person

Event message:

  • Leakage current-carrying capacity of DC generator too high.

Explanation:

The permissible residual current reaches or exceeds the threshold.

Corrective measures:

  • If a residual-current device is installed, ensure that it is set correctly.

  • Observe the behavior of the inverter and wait to see whether the inverter resumes operation on its own.

  • Ensure that no insulation error is present and that the residual-current device is functional.