Setting phase-exact zero feed-in
Qualified person
To set the phase-exact zero feed-in, the corresponding parameters must be set in the subordinate inverters and the system.
With phase-exact zero export, the grid feed-in is individually monitored on all three grid conductors. As soon as grid feed-in still occurs on a line conductor, the total feed-in power is reduced. This procedure is mandatory in some countries and may lead to increased grid-supplied power.
Requirements:
- The user interface must be open and you must be logged in as Installer.
- The parameter External active power setting, limitation of change rate must be disabled in the subordinate inverter.
- The parameter External active power setting 2, limitation of change rate must be disabled in the subordinate inverter.
- The parameter External active power setting, nominal value filter must be disabled in the subordinate inverter.
- The parameter External active power setting 2, nominal value filter must be disabled in the subordinate inverter.
- Optimized closed-loop/open-loop control must be activated under Operating mode for active power ( > Configuring active and reactive power setpoints).
Procedure:
- Select the system in the focus navigation.
- Select the menu Configuration.
- Select the menu item Grid management services.
- Select Configuration & activation under Active and reactive power.
- Open the sub-item Grid operator specifications in the Active power area.
- Activate Manual setpoint for active power limitation.
- Activate the button Phase-exact zero active power feed-in.
- Click on [Save].