Use of one or multiple digital outputs (MFR)
The digital output (MFR) can be switched depending on measured values or states.
You have several options to use the digital output.
Possible use | Category | Explanation |
|---|---|---|
Notification in the event of an error | System state | System is in warning or error state. |
Alarm in case of warning or error | System state | System is in error state. |
Direct selling enabled | System state | The active power limitation of the direct seller is currently used for the point of interconnection. |
Battery state of charge1) | Monitoring | Balanced state of charge of all batteries in the system |
System active power1) | Monitoring | Sum of the active power of all PV inverters in the system. |
System reactive power1) | Monitoring | Balance of the reactive power of all selected PV inverters in the system. |
Reactive power setpoint1) | Setpoints | Reactive power value to be set. |
Setpoint of active power limitation1) | Setpoints | The active power value currently to be set. |
Standardized measured voltage value for Q(V)1) | Point of interconnection | Standardized measured voltage value from the point of interconnection. For this, you require a valid Q(V) configuration in the grid management services. |
System active power (grid-supplied power)1) | Point of interconnection | Currently drawn active power. |
System active power (grid feed-in)1) | Point of interconnection | Currently fed-in active power. |
System reactive power at the grid connection point1) | Point of interconnection | Current reactive power. |
1) Conditions for activating the outlet signal must be specified