Setting Zero Export
Qualified person
Requirements:
- The user interface must be open and you must be logged in as Installer.
- The parameter External active power setting, limitation of change rate must be disabled in the subordinate inverter.
- The parameter External active power setting 2, limitation of change rate must be disabled in the subordinate inverter.
- The parameter External active power setting, nominal value filter must be disabled in the subordinate inverter.
- The parameter External active power setting 2, nominal value filter must be disabled in the subordinate inverter.
- Optimized closed-loop/open-loop control must be activated under Operating mode for active power ( > Configuring active and reactive power setpoints).
Procedure:
- Select the system in the focus navigation.
- Select the menu Configuration.
- Select the menu item Grid management services.
- Select Configuration & activation under Active and reactive power.
- Open the sub-item Grid operator specifications in the Active power area.
- Activate Manual setpoint for active power limitation.
- Adjust the value to 0%.
- Click on [Save].