Setting Zero Export
Qualified person
To set the phase-exact zero feed-in, the corresponding parameters must be set in the subordinate inverters and the system.
With phase-exact zero export, the grid feed-in is individually monitored on all three grid conductors. As soon as grid feed-in still occurs on a line conductor, the total feed-in power is reduced. This procedure is mandatory in some countries and may lead to increased grid-supplied power.
Requirements:
The user interface must be open and you must be logged in as Installer.
The parameter External active power setting, limitation of change rate must be disabled in the subordinate inverter.
The parameter External active power setting 2, limitation of change rate must be disabled in the subordinate inverter.
The parameter External active power setting, nominal value filter must be disabled in the subordinate inverter.
The parameter External active power setting 2, nominal value filter must be disabled in the subordinate inverter.
Optimized closed-loop/open-loop control must be activated under Operating mode for active power ( > Configuring active and reactive power setpoints).
Procedure:
- Select the system in the focus navigation.
- Select the menu Configuration.
- Select the menu item Grid management services.
- Select Configuration & activation under Active and reactive power.
- Open the sub-item Grid operator specifications in the Active power area.
- Activate Manual setpoint for active power limitation.
- Activate Phase-exact zero active power feed-in.
- Select [Next] and complete the settings on grid management services.
- Click on [Save].