Configuring controllable loads as per §14a EnWG
Requirement:
- The user interface must be open and you must be logged in.
Procedure:
- Select the product in the focus navigation.
- Select the menu Configuration.
- Select the menu item I/O configurations.
- Select the type of the I/O channel Digital input.
- Select the use for the digital input [Limitation of controllable loads].
- Select source of the digital value.
- Select the digital input that is used for limitation.
- If necessary, activate inversion of the signal.
- Assign a name to the I/O channel.
- Click on [Save].
The number of controllable loads is specified via the parameter "Number of controllable loads" (Parameter.PlntCtl.LoadLimit.NbrLoads). (Based on this, the maximum permissible power consumption of all controllable loads is calculated using the diversity factor.)