Adjustable parameters for voltage and frequency monitoring


Qualified person

You can set the following parameters for voltage and frequency monitoring via the user interface of the inverter.

Name

Value/range

Default value

Voltage monitoring upper maximum threshold

1.5 p.u. to 3 p.u.

1.78 p.u.

Voltage monitoring upper max. threshold trip. time

0.1 ms to 5 ms

0.312 ms

Voltage monitoring, upper maximum threshold

1 p.u. to 2 p.u.

1.2 p.u.

Voltage monitoring, upper max. threshold trip. time

0 ms to 1000000 ms

160 ms

Voltage monitoring, median maximum threshold (Overvoltage/Fast)

1 p.u. to 2 p.u.

1.1 p.u.

Voltage monitoring, median max. threshold trip.time (Overvoltage/Fast, maximum time)

0 ms to 1000000 ms

13000 ms

Voltage monitoring lower maximum threshold (Overvoltage/Slow)

1 p.u. to 2 p.u.

1.1 p.u.

Voltage monitoring lower max. threshold trip. time (Overvoltage/Slow, maximum time)

0 ms to 1000000 ms

1000000 ms

Voltage monitoring, upper minimum threshold (Undervoltage/Slow)

0 p.u. to 1 p.u.

0.88 ms

Voltage monitoring, lower min. threshold trip. time (Undervoltage/Slow, maximum time)

0 ms to 1000000 ms

1000000 s

Voltage monitoring, median minimum threshold (Undervoltage/Fast)

0 p.u. to 1 p.u.

0.88 ms

Voltage monitoring, median min. threshold trip.time (Undervoltage/Fast, maximum time)

0 ms to 1000000 ms

21000 ms

Voltage monitoring, lower minimum threshold

0 p.u. to 1 p.u.

0.5 p.u.

Voltage monitoring, lower min. threshold trip. time

0 ms to 1000000 ms

2000 ms

Frequency monitoring median maximum threshold

50 Hz to 66 Hz

62 Hz

Frq. monitoring median max. threshold trip. time (Overfrequency, maximum time)

0 ms to 1000000 ms

160 ms

Frequency monitoring, lower maximum threshold (Overfrequency)

50 Hz to 66 Hz

61.2 Hz

Frequency monitoring, lower max. threshold trip. time

0 ms to 1000000 ms

300000 ms

Frequency monitoring upper minimum threshold (Underfrequency)

44 Hz to 60 Hz

58.5 Hz

Frequency monitoring, upper min. threshold trip. time (Underfrequency, maximum time)

0 ms to 1000000 ms

300000 ms

Frequency monitoring, lower minimum threshold

44 Hz to 60 Hz

56.5 Hz

Frequency monitoring, lower min. threshold trip. time

0 ms to 1000000 ms

160 ms

Volt. increase prot.

1 to 2

2 p.u.

Voltage increase protection trigger time

40 ms to 10000 ms

10000 ms

Max. voltage for reconnection

0 p.u. to 1 p.u.

0.917 p.u.

Min. voltage for reconnection

2 p.u. to 2 p.u.

1.05 p.u.

Rated grid voltage

0.8 p.u. to 1.2 p.u.

1 p.u.